If the M490DEP is held open while a fire alarm is reset, will the maglock go into alarm?
If the M490DEP door is held open during a fire alarm and the fire alarm input is reset with the door still open, it should not alarm. The delayed egress is not set (with the internal plunger at least)...
Schlage Commercial » System Components » Electromagnetic Locks
How does the DSM an MBS contacts function on the M400 Mag Locks?
Door open - DPS contact is in an open state -   Door Closes contact changes state to normally closed   Door open de-energized-  MBS is an open state-  ...
Schlage Commercial » System Components » Electromagnetic Locks
Am I able to run the current for a mag lock through the Von Duprin RX switch?
In general,  it is recommended to use Allegion power supply logic boards,  such as 900-RL (click here) ,    to receive input signals from switches,  and to power out...
Schlage Commercial » System Components » Electromagnetic Locks
Is the Delayed Egress signage included in the Kits for DE?
P23840952         M490DEP BOCA PCB Kit (:15 Sec. Delay) P47261544         M490DEP BOCA PCB Kit (:30 Sec Delay)  The signage mus...
Schlage Commercial » System Components » Electromagnetic Locks
If the M490DE-2 And M490DEP-2 seems to be installed correctly but the alarm keeps going off.
Make sure that in both the master and slave that there is a jumper in both AUX terminals...
Schlage Commercial » System Components » Electromagnetic Locks
Can the M490DE be installed as a side mount?
No, the DE has never been tested for vertical or side mounting, this is not recommended....
Schlage Commercial » System Components | Schlage Commercial » System Components » Electromagnetic Locks
Can you bench test a GF3000 without using the armature plate?
No, the lock needs to see the magnets aligned, the armature triggers the bond....
Schlage Commercial » System Components | Schlage Commercial » System Components » Electromagnetic Locks
What would cause the GF3000 to be hot?
First make sure the control module is installed and the DC power is correct.Confirmed no AC leakage - turn meter to ac should measure 0.  some switching power supplies give ac on the dc and that ...
Schlage Commercial » System Components | Schlage Commercial » System Components » Electromagnetic Locks
When you purchase a GF3000 switch, is the door positioning switch built in the lock or does it come it the box separate?
The GF3000, all versions except the BRD, have the auto relock switch built into the housing standard with the lock. Auto relock is standard on the GF3000, MBS is optional, DSM, is not an option a...
Schlage Commercial » System Components | Schlage Commercial » System Components » Electromagnetic Locks
How much space is recommended on the door frame for mounting a M320 Mag lock?
1 1/2" or more would be recommended to make sure there is plenty of room for mounting but 1 3/8" would be the very minimum....
Schlage Commercial » System Components » Electromagnetic Locks