Category: 6000 Series

(Results from 1 to 10)
What is a Von Duprin 893P strike?
The 893P is not a strike, it is the UL label on a 6000 series strike.  This label will not describe the strike you have....
System Components » Electric Strikes » 6000 Series » Von Duprin | Von Duprin
How to convert the Von Duprin 6000 series electrical strike from Fail Secure to Fail Safe or Fail Safe to Fail Secure?
To convert the Von Duprin 6000 series electric strikes from FS to FSE  or from FSE to FS follow these steps: Remove the electric strike face plate. Remove the strike box cover plate...
System Components » Electric Strikes » 6000 Series » Von Duprin
What electric strikes are available for Von Duprin rim exit devices?
The 22, 33/35A and 98/99 rim exit devices: The 6111 is the most common electric strike to be used with these devices 6112 and 6113 electric strikes also could be used The 6300 surface mount elect...
Exit Devices » Cross Bar » 55 Series » Von Duprin | Exit Devices » Cross Bar » 88 Series » Von Duprin | Exit Devices » Touch Bar » 22 Series » Von Duprin | Exit Devices » Touch Bar » 33A/35A Series » Von Duprin | Exit Devices » Touch Bar » 98/99 Series » Von Duprin | System Components » Electric Strikes » 6000 Series » Von Duprin
What is the replacement for the Locknetics 9100 series electric strike?
The Locknetics 9100 series electric strikes are replaced with Von Duprin 6211 and 6210 electric strikes.   The 6211 is used if the frame is being replaced. The 6210 is for exi...
System Components » Electric Strikes » 6000 Series » Von Duprin
Can the electric strike be used with a vertical rod device on a fire-rated door?
The 6111 electric strike can be used only on non rated openings less bottom rod with pullman top latch (use ES prefix when ordering device). Device back set will change to match the centerline of t...
Exit Devices » Touch Bar » 98/99 Series » Von Duprin | System Components » Electric Strikes » 6000 Series » Von Duprin
What questions should be asked to determine which Von Duprin 6000 series electric strike I have?
Follow these questions to determine which Von Duprin electric strike model you have 1. What type of hardware is latching to the electric strike?   2. Single or pair of ...
System Components » Electric Strikes » 6000 Series » Von Duprin
Are the wires on a Von Duprin 6000 series electric strike polarized?
The wires on 6000 series electric strike solenoid are non polarized....
System Components » Electric Strikes » 6000 Series » Von Duprin
What electric strike can be used on a pair of doors with an L9000 lock?
Von Duprin 6223 electric strike is the most common closed back strike or the 6221 for open back strike on inactive leaf that can be used with Schlage L9000 or Von Duprin 7500 mortise lock....
Mechanical Locks » Mortised » L9000 Series » Schlage | System Components » Electric Strikes » 6000 Series » Von Duprin
Does Von Duprin have a repair department?
Von Duprin and Falcon do not offer repair services for any of its exit devices....
Exit Devices » Cross Bar » 55 Series » Von Duprin | Exit Devices » Cross Bar » 88 Series » Von Duprin | Exit Devices » Touch Bar » 22 Series » Von Duprin | Exit Devices » Touch Bar » 33A/35A Series » Von Duprin | Exit Devices » Touch Bar » 98/99 Series » Von Duprin | Power Supplies » Standard » PS900 Series » Von Duprin | System Components » Electric Strikes » 4000 Series » Von Duprin | System Components » Electric Strikes » 5100 Series » Von Duprin | System Components » Electric Strikes » 6000 Series » Von Duprin | System Components » Electric Strikes » 6300 Series » Von Duprin
Is the Von Duprin 6111 electric strike compatible with Von Duprin XP98/99 rim exit device?
This is not a recommended application as the electric strike does not have the same holding force as the XP98/99 rim exit device. The electric strike has 1500 pounds of holding force whereas the XP98/...
Exit Devices » Touch Bar » 98/99 Series » Von Duprin | System Components » Electric Strikes » 6000 Series » Von Duprin