Category: Automatic Operator

(Results from 11 to 20)
Can a wireless actuator be converted to hardwired?
Yes. Remove the receiver from the operator. Remove the transmitter from the actuator button. Attach 1 wire to the NO (normally open) contact on the actuator switch, and another wire to the COM (co...
Automatic Operators » Electrohydraulic » 4630 Series » LCN | Automatic Operators » Electromechanical » Benchmark » LCN | Automatic Operators » Electromechanical » Senior Swing » LCN | Automatic Operators » Pneumatics » 2610 Series » LCN | Automatic Operators » Pneumatics » 4810 Series » LCN | Door Controls » Automatic Operator » 7900 Series » LCN | Door Controls » Automatic Operator » 7980 Series » LCN | Door Controls » Automatic Operator » 8310 Series » LCN
Can you power a electric strike from the 7900 control boxes?
The power supply output in the 7900 series control box is a 12VDC output, rated at (1/4A) 0.250A. It cannot be used to power a strike or maglock. You need to have a separate power supply for the str...
Door Controls » Automatic Operator » 7900 Series » LCN | Door Controls » Automatic Operator » 7980 Series » LCN
What is the minimum and maximum PSI applied to a 4800 operator?
The pneumatic operators are designed to function with an input air pressure to the 7901/7902 Series control box of 80 (min) 100 (max) PSI, and an output pressure of 60 to 80 PSI to the pneumatic (26...
Automatic Operators » Pneumatics » 4810 Series » LCN | Door Controls » Automatic Operator » 7900 Series » LCN
What are Pneumatic Automatic Operators?
 Pneumatic Automatic Operators are used in areas where electrically operated devices are not convenient or permitted.  Consists of a modified, heavy-duty door closer for manual operati...
Automatic Operators » Pneumatics » 2610 Series » LCN | Automatic Operators » Pneumatics » 4810 Series » LCN | Door Controls » Automatic Operator » 7900 Series » LCN | LCN
How do you program the 8310-865 RF receiver?
To program the 8310-865 receiver: Set the dip switches 1 to the "OFF" (pulse) position. Set the dip switches 2 to the "OFF" (0.5s) position. Momentarily press the " No Delay" or "Del...
Door Controls » Automatic Operator » 8310 Series » LCN
What wire gauge is recommended for LCN hardwired actuators?
LCN recommends an 18 AWG (minimum) wire size (gauge) to the 8310 Series hardwired actuators....
Door Controls » Automatic Operator » 8310 Series » LCN
Why would an 8310-865 RF Receiver for power operator have a flashing "RED" light?
When the "RED" LED on the 8310-865 RF Receiver is blinking, it is receiving an RF signal (interference) from a non programmed device. When receiving this type of signal, it will not program correct...
Door Controls » Automatic Operator » 8310 Series » LCN
8310-865 receiver and sequence.
RF sequential operation requires the use of of a minimum of 2 receivers (8310-865). Depending on the desired operation required (if using access control), it may require up to 4 receivers (8310-865). ...
Door Controls » Automatic Operator » 8310 Series » LCN
What is the 7910-956 direct crossover?
The 7910-956 actuator direct replacement is the 8310-856 actuator....
Door Controls » Automatic Operator » 8310 Series » LCN
What actuators can be used on the 8310-866 Bollard post?
The LCN Bollard post (8310-866) only accepts the "square" actuators (no round actuators). The size of the Bollard post is 4” X 6” X 36”. Acceptable actuator part numbers are: Hard Wired - ...
Door Controls » Automatic Operator » 8310 Series » LCN