What electric strikes can be used with the Von Duprin aluminum mullions?
Aluminum mullions 5654 or 5754 are not designed to accept any electric strike including 6300 surface mounted electric strike....
Schlage Commercial » Exit Devices » Mechanical Accessories » Mullion » Von Duprin | Schlage Commercial » System Components » Electric Strikes » 6000 Series » Von Duprin | Schlage Commercial » System Components » Electric Strikes » 6300 Series » Von Duprin
Can the 5100 electric strike be used with mortise locks?
...
Schlage Commercial » System Components » Electric Strikes » 5100 Series » Von Duprin | Schlage Commercial » System Components » Electric Strikes » 6000 Series » Von Duprin
What power supply is required to operate the 6000 series electric strike?
Option boards are not required with PS900 series power supplies when using electric strikes. See the list of options below. The PS902 would power up to 5 electric strikes at 24VDC or ...
Schlage Commercial » Power Supplies » Standard » PS900 Series » Von Duprin | Schlage Commercial » System Components » Electric Strikes » 6000 Series » Von Duprin
How to convert the Von Duprin 6000 series electrical strike from Fail Secure to Fail Safe or Fail Safe to Fail Secure?
Part numbers: FS slider, part # 090591  (Use for all EXCEPT 6211WF/6212WF/6221/6223. See 090798 below)   FS slider, part #090798 (Use this slider for FS models 6211WF/6...
Schlage Commercial » System Components » Electric Strikes » 6000 Series » Von Duprin
How hot do the 6000 electric strikes get?
If the solenoid of the 6000 series electric strike is powered continuously with proper voltage at room temperature, the solenoid can feel very warm to the touch.  Ensure the power supply is ...
Schlage Commercial » System Components » Electric Strikes » 6000 Series » Von Duprin
Can you use a 6111 electric strike with a 7000 series Yale device?
The 6111 can not be used with the Yale 7000 devices as the exit device latch is too far from the face of the door.  ...
Schlage Commercial » System Components » Electric Strikes » 6000 Series » Von Duprin
Why would a 6111 blow fuse?
Either a bad solenoid or short to ground.Check resistance, 12VDC solenoid measures 21 Ohms and 24VDC solenoid measures 70 Ohms.Check for a short to ground in the wiring between power supply and e...
Schlage Commercial » System Components » Electric Strikes » 6000 Series » Von Duprin
Which electric strike to use with a DOM 2090 device?
A Von Duprin 6113, 6300, or any electric strike that would work with a rim Exit device that is comparable to the DOM 2090....
Schlage Commercial » Exit Devices » Cross Bar » 2090 Series » Falcon | Schlage Commercial » System Components » Electric Strikes » 6000 Series » Von Duprin
Why would an electric strike not stay locked when turned upside down?
The Von Duprin 6000 series electric strike has a 12 or 24VDC solenoid with plunger, spring and impact washer as shown 6000 solenoid Make sure the solenoid spring and impact washer are not missing....
Schlage Commercial » System Components » Electric Strikes » 6000 Series » Von Duprin
Can the electric strike be used in an outdoor application?
Electric strikes are not water proof an not recommended for exterior application especially gates....