Category: Von Duprin

(Results from 11 to 20)
Does Von Duprin have a repair department?
Von Duprin and Falcon do not offer repair services for any of its exit devices....
Schlage Commercial » Exit Devices » Cross Bar » 55 Series » Von Duprin | Schlage Commercial » Exit Devices » Cross Bar » 88 Series » Von Duprin | Schlage Commercial » Exit Devices » Touch Bar » 22 Series » Von Duprin | Schlage Commercial » Exit Devices » Touch Bar » 33A/35A Series » Von Duprin | Schlage Commercial » Exit Devices » Touch Bar » 98/99 Series » Von Duprin | Schlage Commercial » Power Supplies » Standard » PS900 Series » Von Duprin | Schlage Commercial » System Components » Electric Strikes » 4000 Series » Von Duprin | Schlage Commercial » System Components » Electric Strikes » 5100 Series » Von Duprin | Schlage Commercial » System Components » Electric Strikes » 6000 Series » Von Duprin | Schlage Commercial » System Components » Electric Strikes » 6300 Series » Von Duprin
Is the Von Duprin 6111 electric strike compatible with Von Duprin XP98/99 rim exit device?
This is not a recommended application as the electric strike does not have the same holding force as the XP98/99 rim exit device. Typically the XP device will withstand a higher force than electric ...
Schlage Commercial » Exit Devices » Touch Bar » 98/99 Series » Von Duprin | Schlage Commercial » System Components » Electric Strikes » 6000 Series » Von Duprin
Do we have an electric strike for use w/ a mortise lock w/ deadbolt for wood frame?
The 6216 electric strike was designed only for use with only the Folger Adams 310-3-1 mortise lock with deadbolt. The dead bolt must be retracted manually for the the strike to operate....
Schlage Commercial » System Components » Electric Strikes » 6000 Series » Von Duprin
What is the correct centerline for the 6211 with the BEST 45 H mortise lock?
Center line of the 45H mortise lock and center line of the 6211 electric strike are the same.  (both on the same center line)...
Schlage Commercial » System Components » Electric Strikes » 6000 Series » Von Duprin
What took place of the 3140 strike?
The Von Duprin 3140 electric strike is discontinued and the direct replacement is 6211 electric strike....
Schlage Commercial » System Components » Electric Strikes » 6000 Series » Von Duprin
Can a DPS switch and two 6300 strikes be ran off a PS902?
DPS switch is not a load and is not a factor in sizing the Power Supply.  The PS902 will power two 6300 electric strikes no problem....
Schlage Commercial » System Components » Electric Strikes » 6000 Series » Von Duprin | Schlage Commercial » System Components » Electric Strikes » 6300 Series » Von Duprin
Should a solenoid be hot to the touch?
If there is concern that the solenoid or device is "too hot" or has the capability to cause injury, disconnect the device and contact a authorized service representative to analyze the opening....
Schlage Commercial » System Components » Electric Strikes » 6000 Series » Von Duprin | Schlage Commercial » Von Duprin
What electric strike will work with mortise lock and aluminum 1 1/2" faced frame?
Von Duprin doesn't offer any electric strike to fit into 1 1/2" aluminum/metal faced frame.  Minimum requirement to install 6211/6211AL is 1 15/32" mortise depth....
Schlage Commercial » System Components » Electric Strikes » 6000 Series » Von Duprin
What is the electric strike that replaced the 3042?
The 6213 electric strike replaced the 3042 electric strike....
Schlage Commercial » System Components » Electric Strikes » 6000 Series » Von Duprin
How to determine the voltage used by a 6000 series electric strike?
For all models of 6000 series electric strike, except the 6300 & 6400, the color of the solenoid wires determine the voltage.  Black wires are used on 24VDC solenoids and yellow wires ...
Schlage Commercial » System Components » Electric Strikes » 6000 Series » Von Duprin