Is the Schlage trim CO-100 993 compatible with Von Duprin 8875?
No.   The CO-100 is available with the devices listed on this reference sheet:  http://us.allegion.com/content/dam/allegion-us-2/web-documents-2/DataSheet/Schlage_CO_Series_Exit_Trim_Co...
Schlage Commercial » Exit Devices
I have a trim template. Where is the exit device template information?
The exit device will have a separate template.  The specific template will be based upon the device model.To find all templates,  go to US.Allegion.com and search the documents library....
Schlage Commercial » Exit Devices
Is it possible to convert Von Duprin 2227 (surface vertical rod) to less bottom rod on a rated opening?
Less Bottom Rod (LBR)  has been tested with 499F and fire pin.Order 050171-32 and install strikes and fire pin.  ...
Schlage Commercial » Exit Devices
What template should be used for Falcon F-25-C-WDC on a 20 minute door?
You must use either a 5" metal wrapped edge or full steel channel.The 20 minute device was discontinued in 2013 - templates are still out there for the discontinued 20 minute devices for anyone that h...
Schlage Commercial » Exit Devices
What is the minimum length of a CDSI cover plate?
can cut down to 6"...
Schlage Commercial » Exit Devices
How do I order the following product to carry a fire label: 98L-DT 996 3'?
Order using this format:  98L-F 996DT 3'...
Schlage Commercial » Exit Devices
Is the Von Duprin Guard X 2670 device hurricane rated (HH)?
The HH2670 is only approved for use on single flush doors per NOA 15-0826.23 and FBC FL#12400.3.  It is shown using the 267 strike and has a design pressure rating of +/-55 PSF. ...
Schlage Commercial » Exit Devices | Schlage Commercial » Exit Devices » Touch Bar » Guard X | Schlage Commercial » Exit Devices » Touch Bar » Guard X » Von Duprin
What does the term dogging mean?
See link here....
Schlage Commercial » Exit Devices | Schlage Commercial » Von Duprin | Schlage Commercial
On a 9927 surface vertical device, can dead locking feature on the top latch be removed so that it can be used with an electric strike?
For this case,  order 050402-00 pullman latch kit.Please contact Von Duprin product support to review your specific application....
Schlage Commercial » Exit Devices
Can the 33 series Concealed vertical rods (3347) be used on wood doors?
In most cases, the 9947 or 9950 devices would be used on solid wood doors.But, the 3347 or 3350 devices can be used on wood doors if desired.Contact Allegion product support if you would like to revie...
Schlage Commercial » Exit Devices