101+ or 390DEL After memory clear Relock delay may reset to 1 second.
If memory is cleared on delayed egress maglocks they may revert to a 1 second relock time. The relock delay will need to be reset to a value between 6 - 8 seconds. The max delay is 30 seconds....
Schlage Commercial » System Components » Electromagnetic Locks » 101+ Series » Schlage Electronics | Schlage Commercial » System Components » Electromagnetic Locks » 390DEL Series » Schlage Electronics
Does the 101+ or 390DEL require a spike supressor?
The 101+ and 390DEL mag locks have built in spike suppression. There should not be any type of diode, resistor, or supression put at terminals 1 and 2. can cause residual magnetism ...
Schlage Commercial » System Components » Electromagnetic Locks » 101+ Series » Schlage Electronics | Schlage Commercial » System Components » Electromagnetic Locks » 390DEL Series » Schlage Electronics
New Delay Egress Maglock Replacing the 390DEL and 101+
The 390DEL and 101+ maglocks have been discontinued.
They are being replaced within the product line to the M490DE, a plunger-switch activated delayed egress maglock much like the 390DEL....
Schlage Commercial » System Components » Electromagnetic Locks » 101+ Series » Schlage Electronics | Schlage Commercial » System Components » Electromagnetic Locks » 390DEL Series » Schlage Electronics
101+ or 390DEL not locking
Check power at terminals 1 and 2 (12 or 24V AC/DC ).When lock has power but will not lock check dip switch SW4-7 (Automatic Relock) and ensure it is on.[101+ only] Ensure SW1 the red slide switch is i...
Schlage Commercial » System Components » Electromagnetic Locks » 101+ Series » Schlage Electronics | Schlage Commercial » System Components » Electromagnetic Locks » 390DEL Series » Schlage Electronics
390 DEL System 7 Programming swich positioning.
When using system seven programming, ensure proper switch positioning. Locate the SW4 dip switch bank, Set the Number 1 position to off when programming ibuttons. If SW4, posit...
Schlage Commercial » System Components » Electromagnetic Locks » 101+ Series » Schlage Electronics | Schlage Commercial » System Components » Electromagnetic Locks » 390DEL Series » Schlage Electronics
390 DEL-2 vs 101-2+ Master and Slave Replacement Units
The nearest functional equivalent to replace the legacy Master slave delayed egress mag locks is the M490DE-2 or M490DEP-2....
Schlage Commercial » System Components » Electromagnetic Locks » 101+ Series » Schlage Electronics | Schlage Commercial » System Components » Electromagnetic Locks » 390DEL Series » Schlage Electronics | Schlage Commercial » System Components » Electromagnetic Locks » M400 Series
390DEL MBS not functioning
If Magnetic Bond Sensor (MBS) is not changing states:Ensure that MBS test is being performed by bonding to a properly aligned armature. The Bond sensor is calibrated to the mas of the armature at...
Schlage Commercial » System Components » Electromagnetic Locks » 390DEL Series » Schlage Electronics
390DEL Solid Amber Light
If 390DEL amber light stays on solid after disabling the delayed egress function, make sure nothing is tied into terminals 5 and 6. A closure here will allow the lock to function properly but wi...
Schlage Commercial » System Components » Electromagnetic Locks » 390DEL Series » Schlage Electronics