Category: Von Duprin

(Results from 1 to 10)
Can you power an electric strike or maglock from the 9500 Series Senior Swing?
An electric strike or maglock (24 volt only) can be wired to a Senior Swing 2800/9500 series operator using the P10 Lock Interface cable.For Current Sr Swing control boxes with ID# 72940 on the s...
Schlage Commercial » Automatic Operators » Electromechanical » Senior Swing » LCN | Schlage Commercial » System Components » Electrified System Component Accessories » Rectifier » Von Duprin
Can 24 volts be run to a 12 volt 6000 series electric strike solenoid?
You can't run 24VDC into the 12VDC electric strike, over voltage such as this will cause the solenoid to heat up and damage the solenoid.  You must change to a 24V solenoid, part number 050240-00....
Schlage Commercial » System Components » Electric Strikes » 6000 Series » Von Duprin | Schlage Commercial » System Components » Electrified System Component Accessories » Rectifier » Von Duprin
What is the part number for SO24 rectifier?
The part number for the SO24 rectifier is 010058-00....
Schlage Commercial » System Components » Electrified System Component Accessories » Rectifier » Von Duprin
How is the QEL calibrated?
The QELA motor that has shipped since 2015 is self calibrating. Older versions had a calibration button, and these notes would apply: Calibration is an internal process of the QEL device&nbs...
Schlage Commercial » Exit Devices » Recessed » 94/95 Series INPACT » Von Duprin | Schlage Commercial » Exit Devices » Touch Bar » 33A/35A Series » Von Duprin | Schlage Commercial » Exit Devices » Touch Bar » 98/99 Series » Von Duprin | Schlage Commercial » Power Supplies » Standard » PS900 Series » Von Duprin | Schlage Commercial » System Components » Electrified System Component Accessories » Rectifier » Von Duprin | Schlage Commercial » Von Duprin
How do I identify the voltage on the rotary solenoid for E360/E370 Series lever controls?
The wires are white for both 12 and 24 VDC solenoids for Von Duprin lever controls. The last 3 digits on the solenoid sticker identify the voltage: -032= 12VDC -034= 24VDC ...
Schlage Commercial » System Components » Electrified System Component Accessories » Rectifier » Von Duprin | Schlage Commercial » Von Duprin
Can the Function of an M996L be changed without connecting to a power supply?
The function of the M996L can be changed from FS to FSE or from FSE to FS with the use of a 9-volt battery.  *Please note, it needs to be a battery with a high charge or it it will be insuffic...
Schlage Commercial » Exit Devices » Touch Bar » 98/99 Series » Von Duprin | Schlage Commercial » System Components » Electrified System Component Accessories » Rectifier » Von Duprin
Can the M996L be change to fail secure (FSE) before connecting it to a power supply.
A New 9-volt battery can be connected to the leads of the M996 motor to change the function. An older battery may not work. Change the function switch to FSE. Connect the 9V battery to...
Schlage Commercial » Exit Devices » Touch Bar » 98/99 Series » Von Duprin | Schlage Commercial » System Components » Electrified System Component Accessories » Rectifier » Von Duprin | Schlage Commercial » Von Duprin
What is the difference between the M996L and E996L?
The E996L uses a solenoid. It is field selectable for fail safe or fail secure operation. It is only available with a24VDC solenoid. The M996L uses a motor. It is field selectable for fail safe or fai...
Schlage Commercial » Exit Devices » Touch Bar » 98/99 Series » Von Duprin | Schlage Commercial » Exit Devices » Touch Bar » Guard X » Von Duprin | Schlage Commercial » System Components » Electrified System Component Accessories » Rectifier » Von Duprin
Where does the EL dogging rod retaining nut go on the dogging rod?
The retaining nut located under the EL adjustment bushing should be located at the very end of the EL dogging rod...
Schlage Commercial » Exit Devices » Touch Bar » 33A/35A Series | Schlage Commercial » Exit Devices » Touch Bar » 98/99 Series | Schlage Commercial » System Components » Electrified System Component Accessories » Rectifier » Von Duprin | Schlage Commercial » Von Duprin
If my Von Duprin Chexit is armed, will my exterior key retract the latch?
NO, when the Von Duprin Chexit is “armed” the outside key cylinder will NOT operate.   The external inhibit contact must be “opened” across the green/red wire.  ...
Schlage Commercial » System Components » Electrified System Component Accessories » Rectifier » Von Duprin