How many Von Duprin QEL devices can be connected to a power supply?
Product Ordered after 7/10/2012 - Product identified by label on QEL motor You no longer need to use the 900-2Q option board (no longer available) with the PS900 power supplies to ope...
Power Supplies » Standard » PS900 Series » Von Duprin
What are the amperage and power supply requirements for the Von Duprin Chexit (CX) devices?
Chexit motor driven devices shipped after 8-24-2015:You can use 1 Chexit device with PS902, 3 Chexit devices with PS904, and 4 Chexit devices with PS914 or PS906 power supplies with proper gauge ...
Exit Devices » Touch Bar » 98/99 Series » Von Duprin | Power Supplies » Standard » PS900 Series » Von Duprin
What power supply is needed for EL devices?
The Von Duprin PS914 power supply must be used on the EL devices with either the 900-2RS or 900-4RL option board since the EL devices requires power supplies set at 24VDC to be able to provide the 16...
Power Supplies » Standard » PS900 Series » Von Duprin
What power supply do I need for my 2 QELA devices with LCN auto operator?
Use the PS902-2RS power supply with LCN auto operator on single door, PS904-2RS power supply on double door and PS904/906-2RS-2RS for 2 pair of QELA is required for basic operation with actu...
Automatic Operators » Electrohydraulic » 4630 Series » LCN | Automatic Operators » Electromechanical » 8200 Series » Falcon | Automatic Operators » Electromechanical » Benchmark » LCN | Automatic Operators » Electromechanical » Senior Swing » LCN | Door Controls » Automatic Operator » 7900 Series » LCN | Door Controls » Automatic Operator » 7980 Series » LCN | Power Supplies » Standard » PS900 Series » Von Duprin
Is there a wiring diagram for EL and Von Duprin PS914-2RS power supply?
Reference The 914 Installation instructions....
Power Supplies » Standard » PS900 Series » Von Duprin
What wire gauge and run is recommended for Von Duprin electric latch retraction EL device?
  For Product Shipped Prior to August 2012 using the old (black) potted module: a.       0-100 ft 14 gauge wire b.      0-200 ft 12 ga...
Exit Devices » Recessed » 94/95 Series INPACT » Von Duprin | Exit Devices » Touch Bar » 33A/35A Series » Von Duprin | Exit Devices » Touch Bar » 98/99 Series » Von Duprin | Power Supplies » Standard » PS900 Series » Von Duprin
How is the QEL calibrated?
Calibration is an internal process of the QEL device when energized the 1st time.  The solenoid will pull and drop 3 times on a standard calibration.  Calibration can be forced by press...
Exit Devices » Recessed » 94/95 Series INPACT » Von Duprin | Exit Devices » Touch Bar » 33A/35A Series » Von Duprin | Exit Devices » Touch Bar » 98/99 Series » Von Duprin | Power Supplies » Standard » PS900 Series » Von Duprin | System Components » Electrified System Component Accessories » Rectifier » Von Duprin | Von Duprin
What would cause an EL device to pull and release?
If your Von Duprin EL (solenoid) device pulls and releases quickly instead of holding the latch retracted, please check all of the items below.In most cases, one or more of these solutions will reso...
Exit Devices » Touch Bar » 33A/35A Series » Von Duprin | Exit Devices » Touch Bar » 98/99 Series » Von Duprin | Power Supplies » Standard » PS900 Series » Von Duprin
Will the Von Duprin PS902 power supply operate the QEL device?
The Von Duprin PS902 power supply will operate the QEL device as long as you also use the 900-2Q board for devices shipped prior to September of 2012.  After July of 2012, the 900-2RS board ...
Power Supplies » Standard » PS900 Series » Von Duprin
What replaces the Von Duprin PS873 power supply?
The standard Von Duprin PS873 power supply was replaced by the PS914 power supply.NOTE: The newer PS900 option cards can NOT be used in the PS873 power supplies. The PS873 option cards also can N...