How do you order a rectifier kit (for AC power) for 6000 series electric strikes?
All 6000 series electric strikes are shipped with solenoids that require DC power.  Rectifier kits can be ordered to convert AC (from your power source) to DC.  Rectifier kit part numbers ar...
Schlage Commercial » Electronic Locks | Schlage Commercial » Power Supplies | Schlage Commercial » Von Duprin
Can the Von Duprin and Schlage PS900 series power supply be used with 277 volt input?
No, the PS900 series power supplies are not tested or rated to operate with input voltage of 277 volts which is sometimes used for commercial lighting systems. 240 volts is the maximum input....
Schlage Commercial » Power Supplies
How many EL devices can be operated from a PS914 power supply?
Maximum of 8.   Please click here to reference datasheet....
Schlage Commercial » Power Supplies
How many QEL devices will operate from the PS902?
Two.   Please click here for instructions. ...
Schlage Commercial » Power Supplies
When the Von Duprin power supplies are ordered with key lock, are the cabinets always keyed alike?
Yes, they are always keyed alike....
Schlage Commercial » Power Supplies
Will the PS914 power supply work with QEL devices?
Yes, the PS914 (with option board) is compatible with QEL devices.  It will not "fry" the QEL device.  The power supply will only put out the amperage that the load (motor) calls for. &...
Schlage Commercial » Exit Devices | Schlage Commercial » Exit Devices » Touch Bar | Schlage Commercial » Exit Devices » Touch Bar » 98/99 Series | Schlage Commercial » Exit Devices » Touch Bar » 98/99 Series » Von Duprin | Schlage Commercial » Power Supplies | Schlage Commercial » Power Supplies » Standard | Schlage Commercial » Power Supplies » Standard » PS900 Series | Schlage Commercial » Von Duprin
The wires are missing from a 900-BBK. would those wires be apart of the back up board, (900-BB) or with batteries (900-BAT)?
The wires are soldered to the 900-BB board.If you need help with replacement parts, contact sales support or product support for further assistance at 877-671-7011.Option 2 is sales support.Optio...
Schlage Commercial » Power Supplies
On Fire Alarm relay on 900-FA, are FA1 and FA2 dry contacts?
Yes...
Schlage Commercial » Power Supplies
The plug cable that connects the PS902 to the option board should come with the PS902?
The plug cable that connects the PS902 to the option board should come with the PS902?The cable is part of the option board. On the 900-2RS, in the top left corner of the board, the cable should be so...
Schlage Commercial » Power Supplies
Is it normal to see voltage between SC and I1 I2 I3 I4 on power supply option board (900-2RS, 900-4RL, 900-4R) terminals?
Yes, it is normal to see floating voltage between the Signal Common (SC) and Input terminals on the power supply option board.  The Input terminals are not Ground terminals, so they are not a val...