Can a Von Duprin delay egress controller DE5101 run a pair of doors?
One Delayed Egress Controller (DE5101) can run two mag locks on a pair of doors, provided the doors are not controlled independently...
Schlage Commercial » Exit Devices » Touch Bar » 98/99 Series » Von Duprin
The Von Duprin 98 or 99 ALK kit will not sound the horn
Followings are the reason for 98/99 exit alarm ALK not sound when push bar is activated. Make sure key switch on exit alarm ALK is turned on, wait for 20 seconds before you activating the pushbar.&...
Schlage Commercial » Exit Devices » Touch Bar » 22 Series » Von Duprin | Schlage Commercial » Exit Devices » Touch Bar » 33A/35A Series » Von Duprin | Schlage Commercial » Exit Devices » Touch Bar » 98/99 Series » Von Duprin
How does the 98-2 or 99-2 double cylinder function affect the outside lever trim?
Double cylinder (-2 or -2SI) features an inside key cylinder which locks or unlocks the outside trim and an outside key cylinder which retracts the latch bolt only (Night latch function).  This i...
Schlage Commercial » Exit Devices » Touch Bar » 98/99 Series » Von Duprin
What is the minimum opening that a Chexit 4' device can be cut down?
The Von Duprin CX 98/99-4 feet Rim devices on single doors with 5/8" stops and the standard 299 roller strike can be field sized to fit a minimum of 40.2" door opening.  This answe...
Schlage Commercial » Exit Devices » Touch Bar » 98/99 Series » Von Duprin
What wire gauge and run is recommended for Von Duprin electric latch retraction EL device?
 ...
Schlage Commercial » Exit Devices » Recessed » 94/95 Series INPACT » Von Duprin | Schlage Commercial » Exit Devices » Touch Bar » 33A/35A Series » Von Duprin | Schlage Commercial » Exit Devices » Touch Bar » 98/99 Series » Von Duprin | Schlage Commercial » Power Supplies » Standard » PS900 Series » Von Duprin
Is the external inhibit option standard on the " new " ALK from Von Duprin?
The current Von Duprin ALK comes standard with the External Inhibit feature....
Schlage Commercial » Exit Devices » Touch Bar » 22 Series » Von Duprin | Schlage Commercial » Exit Devices » Touch Bar » 33A/35A Series » Von Duprin | Schlage Commercial » Exit Devices » Touch Bar » 98/99 Series » Von Duprin
What mullions should be used with XP devices?
The Von Duprin XP98/99 device uses a different strike than standard 98/99 device. The 909 strike is for non fire rated XP devices and the 954 strike is for the fire rated XP device. 49/9954 mullio...
Schlage Commercial » Exit Devices » Mechanical Accessories » Mullion » Von Duprin | Schlage Commercial » Exit Devices » Touch Bar » 98/99 Series » Von Duprin
Can Von Duprin QEL/EL and CX be in the same device?
You can not use these options together on the same device per the following reasons: QEL/EL device retracts the latch bolt of the exit device allowing entry. CX (Chexit) device loc...
Schlage Commercial » Exit Devices » Touch Bar » 33A/35A Series » Von Duprin | Schlage Commercial » Exit Devices » Touch Bar » 98/99 Series » Von Duprin
Can you power an EL device from a senior swing?
Their is not enough power on a Senior Swing to power an EL device, need PS914-2RS/4RL power supply....
Schlage Commercial » Automatic Operators » Electrohydraulic » 4630 Series » LCN | Schlage Commercial » Exit Devices » Touch Bar » 33A/35A Series » Von Duprin | Schlage Commercial » Exit Devices » Touch Bar » 98/99 Series » Von Duprin
Why is my latch not retracting when I depress the push pad on an XP98/99 device?
  Pushing on the push  bar or activating the EL/QEL or the trim on Von Duprin XP98/99 exit device does not retract the latch, it releases the latch only. Door must be pushed or pulled when devic...
Schlage Commercial » Exit Devices » Touch Bar » 98/99 Series » Von Duprin