What would cause my door closer to try and open the door instead of closing it?
For a door closer that tries to open the door instead of closing it:The closer body could be mounted backwards on the door - check instructions for proper closer orientation.It could be the wrong hand...
Schlage Commercial » Automatic Operators » Electrohydraulic » 4630 Series » LCN | Schlage Commercial » Automatic Operators » Electromechanical » 8200 Series » Falcon | Schlage Commercial » Automatic Operators » Electromechanical » Benchmark » LCN | Schlage Commercial » Automatic Operators » Electromechanical » Senior Swing » LCN | Schlage Commercial » Automatic Operators » Pneumatics » 2610 Series » LCN | Schlage Commercial » Automatic Operators » Pneumatics » 4810 Series » LCN | Schlage Commercial » Door Controls » Overhead Concealed » 2010 Series » LCN | Schlage Commercial » Door Controls » Overhead Concealed » 2030 Series » LCN | Schlage Commercial » Door Controls » Concealed » 3030 Series » LCN | Schlage Commercial » Door Controls » Concealed » 3130 Series » LCN | Schlage Commercial » Door Controls » Concealed » 5030 Series » LCN | Schlage Commercial » Door Controls » Fire Life Safety » Fire/Life Safety Series » LCN | Schlage Commercial » Door Controls » High Security » 2210 Series » LCN | Schlage Commercial » Door Controls » High Security » 4210 Series » LCN | Schlage Commercial » Door Controls » High Security » 4510 Series » LCN | Schlage Commercial » Door Controls » Surface Mounted » 1460 Series » LCN | Schlage Commercial » Door Controls » Surface Mounted » 4010 Series » LCN | Schlage Commercial » Door Controls » Surface Mounted » 4020 Series » LCN | Schlage Commercial » Door Controls » Surface Mounted » 4030 Series » LCN | Schlage Commercial » Door Controls » Surface Mounted » 4040 Series » LCN | Schlage Commercial » Door Controls » Surface Mounted » 4110 Series » LCN | Schlage Commercial » Door Controls » Surface Mounted » SC60 Series » Falcon | Schlage Commercial » Door Controls » Surface Mounted » SC70 Series » Falcon | Schlage Commercial » Door Controls » Surface Mounted » SC80 Series » Falcon | Schlage Commercial » Door Controls » Surface Mounted » SC90 Series » Falcon | Schlage Commercial » Door Controls » Surface Mounted » 4000 Series » LCN | Schlage Commercial » LCN
What could cause a 9100 Series Benchmark operator not to open when the actuator is pushed?
If the 9100 Series Benchmark operator does not open when the actuator is pushed: Verify the unit has 120 volts applied to it. Verify the the power light on the control box is on. If not, check th...
Schlage Commercial » Automatic Operators » Electromechanical » Benchmark » LCN
What is power boost on a Senior Swing or Benchmark operator?
  Power Boost is a positive latching feature that increases the latch force, to over come building stack pressure or door weather stripping, etc, if the door stops before comin...
Schlage Commercial » Automatic Operators » Electromechanical » Benchmark » LCN | Schlage Commercial » Automatic Operators » Electromechanical » Senior Swing » LCN
Can an auto operator be installed on a Dutch door?
Yes, an automatic operator can be installed on a Dutch door. The operator must be installed on the top leaf of the Dutch door. Only the top half will open unless the top and bottom leaves (secti...
Schlage Commercial » Automatic Operators » Electrohydraulic » 4630 Series » LCN | Schlage Commercial » Automatic Operators » Electromechanical » 8200 Series » Falcon | Schlage Commercial » Automatic Operators » Electromechanical » Benchmark » LCN | Schlage Commercial » Automatic Operators » Electromechanical » Senior Swing » LCN | Schlage Commercial » Automatic Operators » Pneumatics » 2610 Series » LCN | Schlage Commercial » Automatic Operators » Pneumatics » 4810 Series » LCN | Schlage Commercial » Door Controls » Automatic Operator » 7900 Series » LCN | Schlage Commercial » Door Controls » Automatic Operator » 7980 Series » LCN
The hold open does not adjust on my Benchmark 9100 Series operator.
First check to make sure that the arm was set up properly.  See here for Benchmark installation instructions. It has to do with how the control senses the motor current when pushing the doo...
Schlage Commercial » Automatic Operators » Electromechanical » Benchmark » LCN
Can a wireless actuator be converted to hardwired?
Yes. Remove the receiver from the operator. Remove the transmitter from the actuator button. Attach 1 wire to the NO (normally open) contact on the actuator switch, and another wire to the COM (co...
Schlage Commercial » Automatic Operators » Electrohydraulic » 4630 Series » LCN | Schlage Commercial » Automatic Operators » Electromechanical » Benchmark » LCN | Schlage Commercial » Automatic Operators » Electromechanical » Senior Swing » LCN | Schlage Commercial » Automatic Operators » Pneumatics » 2610 Series » LCN | Schlage Commercial » Automatic Operators » Pneumatics » 4810 Series » LCN | Schlage Commercial » Door Controls » Automatic Operator » 7900 Series » LCN | Schlage Commercial » Door Controls » Automatic Operator » 7980 Series » LCN | Schlage Commercial » Door Controls » Automatic Operator » 8310 Series » LCN
Can a 9100 series Benchmark be used on a high traffic exterior door?
The recommended application for the 9100 series Benchmark operator is low traffic exterior doors, or low/moderate traffic interior doors. The Benchmark series operator "is not" recommended for use on...
Schlage Commercial » Automatic Operators » Electromechanical » Benchmark » LCN
Does LCN offer battery back up for power operators?
In early 2022 LCN launched a battery back up for power operators. Part number is SOLA. The battery back up will allow up to two single operators to cycle at least 100 times after power loss....
Schlage Commercial » Automatic Operators » Electrohydraulic | Schlage Commercial » Automatic Operators » Electrohydraulic » 4630 Series | Schlage Commercial » Automatic Operators » Electrohydraulic » 4630 Series » LCN | Schlage Commercial » Automatic Operators » Electrohydraulic » 4640 Series » LCN | Schlage Commercial » Automatic Operators » Electromechanical » 8200 Series » Falcon | Schlage Commercial » Automatic Operators » Electromechanical » Benchmark | Schlage Commercial » Automatic Operators » Electromechanical » Benchmark » LCN | Schlage Commercial » Automatic Operators » Electromechanical » Senior Swing | Schlage Commercial » Automatic Operators » Electromechanical » Senior Swing » LCN | Schlage Commercial » Door Controls » Automatic Operator » 7900 Series » LCN | Schlage Commercial » Door Controls » Automatic Operator » 7980 Series » LCN | Schlage Commercial » LCN
Can you replace the old 9100 Benchmark II controller with the new 9100 Benchmark III controller?
The current Benchmark III controller (9130-3462, 9140-3462) is a direct replacement for the older Benchmark II controller....
Schlage Commercial » Automatic Operators » Electromechanical » Benchmark » LCN
What would cause a Falcon 8200 (8230/8240) operator to slam the door closed?
The Benchmark 9100 series and Falcon 8200 Series operator will allow the door to slam if: The motor is not connected (plugged into) the controller as the closing speed is controlled by a circ...
Schlage Commercial » Automatic Operators | Schlage Commercial » Automatic Operators » Electromechanical | Schlage Commercial » Automatic Operators » Electromechanical » 8200 Series » Falcon | Schlage Commercial » Automatic Operators » Electromechanical » Benchmark | Schlage Commercial » Automatic Operators » Electromechanical » Benchmark » LCN | Schlage Commercial » Door Controls | Schlage Commercial » LCN | Schlage Commercial