How do you program the 8310-865 RF receiver?
To program the 8310-865 receiver:
Set the dip switches 1 to the "OFF" (pulse) position.
Set the dip switches 2 to the "OFF" (0.5s) position.
Momentarily press the " No Delay" or "Del...
Door Controls » Automatic Operator » 8310 Series » LCN
8310-865 receiver and sequence.
RF sequential operation requires the use of of a minimum of 2 receivers (8310-865). Depending on the desired operation required (if using access control), it may require up to 4 receivers (8310-865).
...
Door Controls » Automatic Operator » 8310 Series » LCN
What actuators can be used on the 8310-866 Bollard post?
The LCN Bollard post (8310-866) only accepts the "square" actuators (no round actuators). The size of the Bollard post is 4” X 6” X 36”.
Acceptable actuator part numbers are:
Hard Wired - ...
Door Controls » Automatic Operator » 8310 Series » LCN
Is the 8310-849 Door Sequencer still available?
The 8310-845 is now a combination "Time Delay Relay / Door Sequence" module.
In 2010 the separate 8310-845 "Time Delay" module and 8310-849 “Door Sequencer” module were combined into a "common...