what electrical options are available with CX device

RELATED FAQS

Question
Answer
Most common issue listed below: Chexit devices shipped after 8-24-2015 with motor driven. The Green wire is not shoeted to the Red wire if no Access Control system is used.If Access Control is us...
 Chexit devices shipped prior to 8-24-2015 with solenoid driven. The GREEN wire is not shorted to the WHITE if no Access Control system is used.If Access Control system is used,...
The Von Duprin Chexit-BOCA has special software. Following is the function of this software: When Chexit device push bar is pushed and goes into alarm it will release in 15/30 sec...
If the Chexit device shipped prior to 8-24-2015  is not adjusted correctly ( Check vertical rod or Mortise finger) without using the door position switch and nuisance delay is&n...
 
Chexit devices shipped after 8-24-2015 with motor driven: The Chexit device will use a 1 1/4" mortise cylinder with straight cam. Schlage cylinder 20-001-114 recommended. CAUTION: The length of t...
Chexit devices shipped prior to 8-24-2015:The CX device will need a 1 1/4" mortise cylinder with a straight cam per page 2 of the installation instructions. A 996L-M for a 1 3/4...
The Von Duprin CX 98/99-4 feet Rim devices on single doors with 5/8" stops and the standard 299 roller strike can be field sized to fit a minimum of 40.2" door opening.  This an...
The Special Von Duprin 2' door device as of 02-07-14 is now shipped with UL Panic Hardware label or UL Fire Exit Hardware label.  The 2’ devices are most commonly used in 5...
To get a dry contact signal from a Chexit device to monitor the alarm, use the blue and brown wires (do not connect the blue to the red)  of the harness connector cable tha...
The EL Wiring Adapter is not needed for a CX device.
If Chexit device LED blink once when you turn the unit on, the External inhibit green wire is not by passed or not connected to the access control normally closed contact.  For devices sh...
Chexit devices shipped after 8-24-2015 with motor driven:Attached is the installation instructions of the the Von Duprin Chexit devices that includes the wiring diagrams.Installation Instructions&n...
Chexit devices shipped before 8-24-2015 with solenoid driven:Attached are the single and double door wiring , cable voltage reading documents for trouble shooting, and the installation in...
Chexit motor driven devices shipped after 8-24-2015:You can use 1 Chexit device with PS902, 3 Chexit devices with PS904, and 4 Chexit devices with PS914 or PS906 power supplies with proper gau...
The hole should be drilled in the field once the end cap is located on the door.  It is a 5/8" hole, that is located 5/16" from the end of the mechanism case. See installation instruction of t...
Schlage Electronics 1910 series horn can be used as an external horn with Von Duprin Chexit device.
For devices shipped after 8-24-2015 with motor driven:  a.       0-200 ft, use  #18 gauge wire b.      0-500 ft, use #14 gauge wir...
For Product Shipped prior to 8-24-2015 with solenoid driven:          a.       0-100 ft, use #14 Gauge Wire      b.&n...
The 6211 would be the most common electric strike to be used with cylindrical locks on a single door application.  Check the template to confirm compatibility with specific cylindrical lock model n...
The NL key override will not open the door while Chexit rim or vertical rod device is in the arm mode.
 Electric latch retraction, EL, devices are only available in 24VDC.
Following information determine number of the Chexit devices that were shipped prior to 8-24-2015 from the factory with solenoid driven can be hooked up to a single Von Duprin PS873 or PS914 p...
The 22, 33/35A and 98/99 rim exit devices: The 6111 is the most common electric strike to be used with these devices 6112 and 6113 electric strikes also could be used The 6300 surface mount el...
This is not available as the CX has it's own RX switch to activate the alarm when it is in the arm mode.
The access control system should provide Common and Normally Closed dry contact that will connect between the green and white wire on the CX 10 wire harness.
Devices were shipped from the factory with motor driven after 8-24-2015. First confirm that you are using PS900 series (902,904,906 or 914) power supply.      1. Mea...
Devices were shipped from the factory with solenoid driven prior to 8-24-2015.  First confirm that you are using a PS873 or PS914 power supply.Measure the DC voltage at the ten wire hardness a...
SD is Special cylinder dogging in the center case of 98/99 rim and vertical rod non fire rated devices and is available with standard, EL, QEL, CX and ALK.
It is recommended to use the Von Duprin EPT10 with CX device but if you need a door loop or electric hinge these are also acceptable. See attached table for wire run and gauge requirements: ...
The Chexit device has a different base plate and center case than the ALK.  The Chexit device would need to be replaced with an ALK device.
You can specify Chexit CX98/9927-LBR or CX98/9947-LBR exit devices.
This configuration is not possible as the anti-pick plate of a "DL" or "F" device center case interferes with the LM/DM switch mounted also on the center case. 
For Motor driven Chexit devices shipped from the factory after 8-24-2015, the Chexit Secure Relay Contacts( white and violet wires) change state to signal the device is not secure. Check the f...
For Solenoid driven Chexit devices shipped from the factory prior to 8-24-2015, the following could cause the device not to provide delay egress:Measure the voltage between green and orange wires o...
Chexit devices shipped with motor after 8-24-2015. 1. When Chexit device is set for more than zero second rearm time (factory setting is 10 second rearm time) and device goes into alarm immediatel...
Chexit devices shipped with solenoid prior to 8-24-2015. 1.  When Chexit device  is set for more than zero second rearm time (factory setting is 10 second rearm time) and device goes...
The release delay time for the Chexit is programmed into the Chexit module and cannot be changed in the field. The Chexit module would need to be replaced to reduce the release time of the Che...
Chexit devices are NOT electric latch retraction.  In order for Chexit device to operate with an auto operator you will need to add a rim electric strike on a single door or a pair o...
Chexit devices shipped prior to 8-24-2015 with solenoid driven: A normally closed card reader contact, key pad contact or any other control contact connects to the Green an...
The standard Von Duprin mechanical or electrical 98/99/33/35 exit devices can not be converted to a CX98/99 or CX33/35 device. Von Duprin CX98/99 or CX33/35 has a different base p...
For Chexit devices shipped after 8-24-2015 with motor driven connect your normally closed contact from access control system between green and red on the twelve field wire ...
When CX99L-BE is not armed with key cylinder on the device or shunted by card reader, the exterior 996LBE lever trim will release.
Chexit devices shipped after 8-24-2015 with motor driven:Use the Alarm Relay Contacts on Field Wiring Cable, blue and brown wires of the Chexit device.Connect the blue wire to +24VDC (red wire on F...
Chexit devices shipped prior to 8-24-2015 with solenoid driven:Use the external alarm contact, blue and brown wire on Chexit device.Connect the blue wire to the red wire and connect the brown wire ...
The E996L-FSE trim is needed if the application requires fail-secure operation from the trim side of the opening. When power is out on Chexit device, E996L-FSE trim will remain locked to ...
Chexit devices shipped after 8-24-2015 with motor driven:If two pin REX connector cable is plugged into the Chexit module and Module REX LED is OFF, the RX switch is defective and needs to be repla...
Chexit devices shipped prior to 8-24-2015 with solenoid driven:If Chexit device goes into alarm with fast flashing red LED after the rearm time, the RX switch may be out of adjustment or defective....
Followings could cause the Chexit device to go into alarm after the rearm time: Chexit devices shipped after 8-24-2015 with motor driven: Module DPS LED is ON DPS switch contact is open: Close t...
Chexit devices shipped prior to 8-24-2015 with solenoid driven: Chexit device has a RX switch with a connector that needs to be connected to the Chexit module otherwise the alarm will sound af...
Chexit devices shipped after 8-24-2015 with motor driven:You can power up to four Chexit devices per PS914 power supply. 0-200' run wire, use #18 gauge.0-500' run wire, use # 14 gauge.
Chexit devices shipped prior to 8-24-2015 with solenoid driven:You can power up to four Chexit devices per PS914 power supply on low traffic doors.0-100' run wire, use #14 gauge.0-200' run wire, us...
You can not use these options together on the same device per the following reasons: QEL/EL device retracts the latch bolt of the exit device allowing entry. CX (Chexit) device locks the p...
As of 1/15/2012 the 94/95 device is available with a QEL electric latch retraction option. See attached bulletin.
Chexit devices shipped prior to 8-24-2015 with solenoid driven could cause the Von Duprin CX solenoid to pull and drop and sound the alarm with solid LED or no LED light after the rear...