hold open fire door closer

RELATED FAQS

Question
Answer
The 1260, 1460, and 4030 regular arm closers on the pullside will allow 180° door opening and can be held open at 180°, frame and trim permitting.
Raceway availability: Optional factory installed raceways are available in doors but are not available in frames. Preparation Info: Steelcraft installs a flexible 1/2" ID steel conduit through the...
 The correct method (process) for setting the hold open is: The 4010 hold open arms are handed, verify correct hand arm. (R or L stamped on main arm) Loosen the hold open nut. Opened the door ...
Steelcraft L-Series and T-Series doors are available (as an option) factory prepared for the Von Duprin InPact exit device. 
The hold open position on a "REG" or "EDA"  hold open arm is set with the door to a few degrees shy of the desired hold open point. To properly set, open the door 5° less then the desired hold open...
A Dutch Door is a door having two separate leaves, hung one over the other: Usually equipped so that both leaves can be operated Usually in single doors applications but sometimes specified ...
Cam Lift hinges can only be used with LCN door closers that have a "Regular" style arm.     Manual Closers: Maximum lift dimension is 3/4". Can not be use EDA, CUSH, or Track Arm door closers...
Steelcraft doors and/or frames do not contain any asbestos. Steelcraft did use asbestos in the following products: Steelcraft S16-Series stile and rail door with flush panel and UL fire door l...
No, LCN does not have an electronic hold open closer (SE/ME Series) that will provide a solid 180° hold open position. The 3130SE has an adjustable hold open position from 85° to 110° maximum. ...
Hold Open Closers & Magnets (Fire/Life safety products) provide a wide range of solutions.  Single or multi-point hold open closers Utilize an electromechanical closer. Hold the door o...
If an ME Series closer creeps shut or will not hold open, Verify proper voltage is being supplied to the closer, if correct Check the on/off switch. Verify the voltage on the 2 pin co...
Yes, Steelcraft doors and/or frames are available and can carry a UL, WH or FM label. The type of fire label (UL, WH or FM) is dictated by the specifications and local building code. Doors ...
This condition can be caused by the "closing speed adjustment" being regulated for a fast closing speed. Try adjusting the closing speed to slow down the closing of the door. If that does not corre...
120V Models: The hold open force on the 2310ME / 4310ME / 4410ME closers is "NOT" adjustable. 24V Models: There is a trimpot adjustment on the circuit board that allows you to "REDUCE" the hold op...
Electrical hinges or a power transfer units are the most commonly used practices to run electric power to locks and/or strikes. Electric Hinges: Most electric hinges will fit into a standard 4 ...
When placing an order for a 4041/4040XP Rw/PA with hold open, it would be ordered as a 4041 /4040XP Hw/PA. For an existing Rw/PA requiring the addition of a hold open function, a hold open arm woul...
The "320G" is the # on a UL sticker attached to the arm of most LCN door closers, and is not a door closer model number.  The "320G" means that the arm is not a mechanical hold open device and OK t...
A UL 20 minute fire rating is the maximum fire rating for a Full Glass (FG) door design. A14-Series door construction: Max fire rating is 20 minute. UL label only FG must use Over-Lapping Stee...
A 4040SE would not hold the door open if it has : No Voltage or Improper Voltage. Check that the track has proper voltage going to it (24V AC/DC or 120V AC). If 120 volts is supplied...
Yes, wood doors can be used and installed in most hollow metal frame applications including FE-Series and DE-Series Double Egress frames. Caution - For fire rated applications the wood door manufa...
Yes, as long as you stay with the like style arm.  Example: replace an RW/PA with HW/PA, replace an EDA with HEDA, or replace a CUSH with HCUSH.
The holding force on an SE/ME Series door closer is approximately 35 lbs. and they can be manually pulled out of hold open with approximately 35 lbs of force.
Yes, Steelcraft doors we are approved up to 48" in height or not to exceed a total 2304 square inches per face. Protective plates are usually flat sheets of metal or plastic applied to one or both...
Make sure that the hold open nut is not on upside down.  The orientation of the hold open nut depends on the mounting. On a Top Jamb "Push Side" mount, the hold open nut would poi...
If a door is being held open by the LCN SEM 7800/1900 magnet or any ME/SE Series Sentronic LCN closer, you can remotely release that door to close by ordering the following parts and wiring per ST ...
GrainTech® is a Steelcraft door option which provides a wood grained pattern which is embossed into both face sheets of the door. GrainTech doors are factory stained and top coated with a cle...