Allegion
Terms of Use
Privacy Policy
Frequently Asked Questions
Ask your question
Entering your question as a complete sentence will provide more accurate results than keywords or phrases.
User questions
FAQs
Category List
“
can hold open arms be used on stairwell doors
”
RELATED FAQS
Question
Answer
What special template (ST) is used with the 2030 closer and a low profile track and roller?
Resolution:
The 2030 closer requires a minimum 1-3/8" top rail on the door for the standard track. For a top rail less than 1-3/8" and as narrow as 1", you could use the l...:
Does a SEH require a door closer?
Resolution:
The SEH is an "electronic holder" (ONLY) that is used to hold open a Fire Rated opening. It requires a door closer to be mounted on the opposite side. It is normally used on an existing opening wit...:
SPRING HOLD-OPEN CUSH ARM
Resolution:
SHCUSH,:
HOLD-OPEN ARM
Resolution:
H, Hold open arm:
HOLD-OPEN LONG ARM
Resolution:
HLONG, Deep Reveals:
How much top rail is needed on a 4041 REG/PA (Rw/PA)?
Resolution:
To install a 4041/4040XP with Rw/PA or Hw/PA arm, you need a minimum of 5-3/8" top rail on the door, measured from the bottom of the stop. If the top rail is less than 5-3/8", you will need to use ...:
Will a 4040 Hw/PA hold open at 180°?
Resolution:
The 4041 Rw/PA and the Hw/PA have the same template. The only difference is the arm. The 4041/4040XP Hw/PA, if mounted to the 180° template, will hold the door open at 180°. Rw/PA is Regular A...:
What would cause a 4040SE not to hold the door open?
Resolution:
A 4040SE would not hold the door open if it has : No Voltage or Improper Voltage. Check that the track has proper voltage going to it (24V AC/DC or 120V AC). If 120 volts is supplied...:
How do you adjust the hold open time on a 4600 (4630/4640) operator?
Resolution:
To adjust the hold open time on a 4600 (4630/4640) operator: Press the "MODE" button on the control box 1 time to get into programming mode. The "YELLOW" mode indicator LED next to "HOLD OPEN TI...:
Can you manually pull a 4040SE out of hold open?
Resolution:
The holding force on an SE/ME Series door closer is approximately 35 lbs. and they can be manually pulled out of hold open with approximately 35 lbs of force. :
Can you replace a regular arm with a hold open with out moving the door closer?
Resolution:
Yes, as long as you stay with the like style arm. Example: replace an RW/PA with HW/PA, replace an EDA with HEDA, or replace a CUSH with HCUSH.:
In what direction should the hold open nut be pointing for a 4041 H closer, up or down?
Resolution:
Make sure that the hold open nut is not on upside down. The orientation of the hold open nut depends on the mounting. On a Top Jamb "Push Side" mount, the hold open nut would poi...:
What do I need to do to make my 4041 Reg/PA a hold open arm?
Resolution:
When placing an order for a 4041/4040XP Rw/PA with hold open, it would be ordered as a 4041 /4040XP Hw/PA. For an existing Rw/PA requiring the addition of a hold open function, a hold open arm woul...:
How to adjust a 4010 hold open arm?
Resolution:
The correct method (process) for setting the hold open is: The 4010 hold open arms are handed, verify correct hand arm. (R or L stamped on main arm) Loosen the hold open nut. Opened the door ...:
How do I set the hold open on my 4040 closer?
Resolution:
The hold open position on a "REG" or "EDA" hold open arm is set with the door to a few degrees shy of the desired hold open point. To properly set, open the door 5° less then the desired hold open...:
What are Hold Open Closers & Magnets?
Resolution:
Hold Open Closers & Magnets (Fire/Life safety products) provide a wide range of solutions. Single or multi-point hold open closers Utilize an electromechanical closer. Hold the door o...:
What is a 320G door closer?
Resolution:
The "320G" is the # on a UL sticker attached to the arm of most LCN door closers, and is not a door closer model number. The "320G" means that the arm is not a mechanical hold open device and OK t...:
What is the difference between an LCN CUSH arm, and an LCN EDA arm?
Resolution:
EDA ARM - The EDA arm is a heavy duty parallel arm mount. The degree of door opening is determined by the template used for mounting. EDA arm closers can only be mounted as a Push Side parallel ar...:
Is the 4040 HEDA arm handed?
Resolution:
The 4041/4040XP HEDA arm is handed because of the hold open feature. The regular EDA arm is not handed.:
When did the 4111 Cush arms become non-handed?
Resolution:
This engineering change did affect the templating of the closer. The stop in the shoe is slightly larger than the original handed cush shoe. The new non-handed arm template locates the closer and s...:
What is the part # for the 4040 HCush arm?
Resolution:
The part number for the 4041/4040XP HCush arm is 4040XP-3049CNS.:
How do you order a 4110 hold open spring cush arm only?
Resolution:
The 4110 hold open spring Cush (Spring H Cush) arm part number is 4110-3049SCNS.:
What is the part # for the 4040 regular arm?
Resolution:
The 4040 regular and hold open arms are different. You would have to get a different arm to convert from regular arm to a hold open function. 4040-3077 for a regular arm. 4040-3077L for a long ...:
What are the 1460 closer arm options?
Resolution:
The 1460 Regular Arm part numbers are: Regular Arm -- 1460-3077 or 1460-3077L for long arm (must specify finish). Regular Arm with PA -- 1460-3077PA (must specify finish). Regular Hold Open Ar...:
What is the narrowest door a 4040 pull side will mount on?
Resolution:
14" door leaf is the narrowest with standard template.:
Why would a 4600 not open a full 90 degrees?
Resolution:
A 4600 (4630/4640) not opening to a full 90 degrees could be caused by a couple things: The Opening Force could be set too low. Try increasing the opening force adjustment on the controller a 1/...:
Can you mount a 4041 Cush arm with a EDA arm template and get 180 degrees opening?
Resolution:
The dead stop post would need to be removed and the 4040/4040XP EDA mounting template for 180° would be followed.:
Can a magnet, or sentronic device, be released and close the door from a button at a desk?
Resolution:
If a door is being held open by the LCN SEM 7800/1900 magnet or any ME/SE Series Sentronic LCN closer, you can remotely release that door to close by ordering the following parts and wiri...:
What are the different door cores available?
Resolution:
The five most common cores are honeycomb, polystyrene, polyurethane, steel stiffened, and temperature rise. Honeycomb core doors are used for interior and exterior openings where high thermal...:
Are the Falcon SC Series door closers fire rated?
Resolution:
Yes, the Falcon SC Series closers have a UL listing.:
Will a 4040SE open and hold at 180°?
Resolution:
No, LCN does not have an electronic hold open closer (SE/ME Series) that will provide a solid 180° hold open position. The 3130SE has an adjustable hold open position from 85° to 110° maximum. ...:
What is the purpose of a Swing Free arm on a 4310ME?
Resolution:
The (SF) "Swing Free" arm allows the door to be put into hold open position, but then repositioned (swing free) to any other degree of opening without taking the closer out of the hold open mode....:
Will CX re-arm if door is held open?
Resolution:
If a door position switch (DPS) is connected across the green and white wires of the old CX (green and red of new CX) the CX would go into alarm if the door is held open when it attempts to rearm.&...: