what wire guage is used for electric strikes

RELATED FAQS

Question
Answer
The 4600 Series operator has both a 12VDC and 24VDC output rated at 1A (combined load) to power strikes, maglocks, and other devices, but an EL device "always" has to have a separate PS914-2RS Seri...
An electric strike or maglock (24 volt only) can be wired to a Senior Swing 2800/9500 series operator using the P10 Lock Interface cable. To power the 24VDC electric strike or maglo...
The 5100 strike details are listed below: Only operates with 12VDC or 24VDC power supply. Will not operate with AC transformer. 12 or 24VAC can be converted to 12/24VDC using Von Duprin SO12 o...
 The 10-042 is an electric strike used for cylindrical and tubular latch sets.    VOLTAGE  24 VAC  12 VDC &n...
The Von Duprin 6000 series electric strike can be converted by ordering the appropriate kits below.  Kits include the solenoid, plunger, spring, and washer. 6000 Series solenoid Kit 12VDC -...
The wires on 6000 series electric strike solenoid are non polarized.
The Benchmark III control has a 24VDC, 2.5 amp power supply, and built in relay for controlling electric strikes or other accessories less than 2.5 amps current load. For a fail secure strike, r...
The 4630/4630 operator has a 12 VDC and 24 VDC output that can power an electric strike or maglock. The wiring diagrams are shown on page 14 of the installation instructions (attached). 4600 Insta...
For all models of 6000 series electric strike, except the 6300 & 6400, the color of the solenoid wires determine the voltage.  Black wires are used on 24VDC solenoids and yellow wir...
The center line of the L9000 mortise lock is 7/8" above the center line of the 6211 electric strike. This is the "C" dimension given on the second page of the 6211 template.
Von Duprin now offers an 8827 LBR panic device as of October 7, 2019. This device uses the top rod assembly and soffit latch setup of the fire rated 8827-F device, but has dogging, a UL Panic Har...
Von Duprin offers a PL8827 LBR device with a pullman style top latch and Less Bottom Rod for use with electric strikes, but is not UL labeled nor ANSI/BHMA certified.
The Von Duprin 5100 electric strike is not for fire rated applications.
Option boards are not required with PS900 series power supplies when using electric strikes. See the list of options below. The PS902 would power up to 5 electric strikes at 24VDC or&n...
The 6211 would be the most common electric strike to be used with cylindrical locks on a single door application.  Check the template to confirm compatibility with specific cylindrical lock model n...
The 22, 33/35A and 98/99 rim exit devices: The 6111 is the most common electric strike to be used with these devices 6112 and 6113 electric strikes also could be used The 6300 surface mount el...
Aluminum mullions 5654 or 5754 are not designed to accept any electric strike including 6300 surface mounted electric strike.
The Falcon 25R rim device can be used with 6111 electric strike on single or double doors. Additional Information: The Von Duprin 4854/9854 mullion is required when using 25R...
For the backset see the Falcon (F)25-R template; T-1201 for Metal Door, W-1201 for Wood Door. For Single Doors, the distance from the surface of the raised stop to the Centerline of the device is...
Electric strikes are not water proof an not recommended for exterior application especially gates.
The 5100 electric strikes are for use with cylindrical locks only.  Instead use the following:6211 electric strike is used with mortise lock without deadbolt on a new single door, hollow ...
The following application information apply to the 5100 electric strike: Can only be used on a single door with a cylindrical lock Can not be used on a pair of doors Can not be used on a mullion
Von Duprin 6223 electric strike is the most common closed back strike or the 6221 for open back strike on inactive leaf that can be used with Schlage L9000 or Von Duprin 7500 mortise lock.
The 6111 electric strike can be used only on non rated openings less bottom rod with pullman top latch (use ES prefix when ordering device). Device back set will change to match the centerline of t...
Not for use in fire rated openings.
To use the 5547 with an electric strike you would need the ES top rod & latch part number 050656-00 and remove the bottom rod and latch. The 6213 electric strike is recommended with 5547LBR, non fi...
The 6111 electric strike would work in this application with a blade stop spacer. The post that it is mounted in should be capped to protect the solenoid from the elements..
EPT can be used on following hinges: Degree of the opening Hinge type Door thickness 0-180 degree Up to 5" butt hinges 1 3/4" 0-180 degree Up to 3/4" offset pivots 1 3/4" 0-130 degree 5 1/2"...
See related solution: Can an EPT be used with Cam Lift Hinges?
The Von Duprin electrified steel mullions, 4854 and 9854 come with a quick connector that connects the electric strike wires from the mullion to the frame through the top fitting.  ...
Electrical hinges or a power transfer units are the most commonly used practices to run electric power to locks and/or strikes. Electric Hinges: Most electric hinges will fit into...
  For Product Shipped Prior to August 2012 using the old (black) potted module: a.       0-100 ft 14 gauge wire b.      0-200 ft 12...
 
This is not a recommended application as the electric strike does not have the same holding force as the XP98/99 rim exit device. The electric strike has 1500 pounds of holding force whereas the XP...
None of the Von Duprin electric strikes will work in a retrofit application where the normal standard mechanical strike is mounted to the frame because none of them are thin enough to fit in...
Von Duprin does not recommend using XP98/99 devices with any electric strike.   Von Duprin recommends using the standard 98/99 rim device.  The XP device has 2000 pound holding forc...
You can't run 24VDC into the 12VDC electric strike, over voltage such as this will cause the solenoid to heat up and damage the solenoid.  You must change to a 24V solenoid, part number 050240-00.