magnetic door holder not holding

RELATED FAQS

Question
Answer
Hold Open Closers & Magnets (Fire/Life safety products) provide a wide range of solutions.  Single or multi-point hold open closers Utilize an electromechanical closer. Hold the door o...
The 4330 / 4430 is an obsolete ME closer replaced by the 4310ME or 4410ME Series.
A 4040SE would not hold the door open if it has : No Voltage or Improper Voltage. Check that the track has proper voltage going to it (24V AC/DC or 120V AC). If 120 volts is supplied...
The top rod is adjusted too short, so when pushpad is pressed it is not operating the top latch enough to get into the hold down position. The top rod would need to be lengthened by turning the lat...
ST-1630 is required when mounting a 4041 or 4040XP door closer regular (pull/hinge) side with a concealed GJ100 or GJ410 series over head stop.
The SEH is an "electronic holder" (ONLY) that is used to hold open a Fire Rated opening. It requires a door closer to be mounted on the opposite side. It is normally used on an existing opening wit...
The holding force on an SE/ME Series door closer is approximately 35 lbs. and they can be manually pulled out of hold open with approximately 35 lbs of force.