dry contact on chexit

RELATED FAQS

Question
Answer
To get a dry contact signal from a Chexit device to monitor the alarm, use the blue and brown wires (do not connect the blue to the red)  of the harness connector cable tha...
Some Access Control Panels are designed with “Supervised” or “Dry contact” requirements for the inputs and have no common ground between the ACP (Access Control Panel) and device at the door. “S...
Schlage offers the “RLBD” to support these supervised or dry contact interface applications. The "RLBD" plugs directly into the PIM400-TD2 or PIB300-TD2 for easy hook-up.  
Please reference this Tehnical Note RLBD SES-20120418 for RLBD setup, use information, hook-up diagrams and some testing suggestions when connecting to a Supervised dry contact Access Contro...
This is a link to the RLBD Installation Instructions.
This RLBD data sheet can also be found at Schlage/Technical Support. RLBD DataSheet
If Chexit device LED blink once when you turn the unit on, the External inhibit green wire is not by passed or not connected to the access control normally closed contact.  For devices sh...
For Motor driven Chexit devices shipped from the factory after 8-24-2015, the Chexit Secure Relay Contacts( white and violet wires) change state to signal the device is not secure. Check the f...
For Solenoid driven Chexit devices shipped from the factory prior to 8-24-2015, the following could cause the device not to provide delay egress:Measure the voltage between green and orange wires o...
The following are needed for a basic installation: Fire alarm contact is always required with Von Duprin Chexit device. 1 1/4" Mortise cylinder with straight cam is required to turn&n...
Chexit devices shipped after 8-24-2015 with motor driven:If two pin REX connector cable is plugged into the Chexit module and Module REX LED is OFF, the RX switch is defective and needs to be repla...
Chexit devices shipped prior to 8-24-2015 with solenoid driven:If Chexit device goes into alarm with fast flashing red LED after the rearm time, the RX switch may be out of adjustment or defective....
Fire alarm contact would tie right into the Von Duprin Chexit device not to the PS914 power supply. There is no requirement to install the fire alarm board.