operators with mag locks
”
RELATED FAQS
Question
Answer
What is the power output of a 4600 operator?
Resolution:
The 4600 Series operator has both a 12VDC and 24VDC output rated at 1A (combined load) to power strikes, maglocks, and other devices, but an EL device "always" has to have a separate PS914-2RS Seri...:
Can the 8200 Series operator power a electric strike?
Resolution:
The 8200 Series operator CANNOT power a strike, maglock, or EL device. A separate power supply is ALWAYS required. There is an onboard relay to control a strike, maglock, or EL device.:
Will the 9100 series Benchmark III power an electric strike?
Resolution:
The Benchmark III control has a 24VDC, 2.5 amp power supply, and built in relay for controlling electric strikes or other accessories less than 2.5 amps current load. For a fail secure strike, r...:
Does the 4600 Series (4630 4640) operator have a built in relay?
Resolution:
Yes, the 4600 Series operators have a built in ES (electric strike) relay that can be used to unlock a strike, maglock, or EL device before opening the door.:
What would cause a 4600 operator to click a few times when the actuator is pushed, but not open the door?
Resolution:
If a 4600 clicks, but won't open the door: Verify proper connection of all the control box connectors. Verify correct manual operation of door. Verify actuator connections and any strike/maglo...:
Does the 9540 Senior Swing need a separate relay board for wiring to electric locks?
Resolution:
The Senior Swing control box has a built in (programmable) relay output for connection to a Fail Safe/Fail Secure electric strike/maglock or to an EL Device power supply.:
Why would a Falcon 8200 Series operator be blowing the fuse?
Resolution:
If the Main AC fuse is blowing, the control box is defective and needs to be replaced. The "Main Fuse" is a (5x20MM) 1 Amp Slow Blow fuse. If the 12VAC fuse is blowing, verify they are not trying...:
What is the input / output of the 8200 series operator?
Resolution:
The Falcon 8200 series operator requires a input of 120 VAC @ 1 Amp.:
How do you wire an electric strike to a 4600 Series operator?
Resolution:
The 4630/4630 operator has a 12 VDC and 24 VDC output that can power an electric strike or maglock. The wiring diagrams are shown on page 14 of the installation instructions (attached). 4600 Insta...:
Can you power an electric strike or maglock from the 9500 Series Senior Swing?
Resolution:
An electric strike or maglock (24 volt only) can be wired to a Senior Swing 2800/9500 series operator using the P10 Lock Interface cable.For Current Sr Swing control boxes with ID# 72940 on th...: