Fire door install instructions

RELATED FAQS

Question
Answer
Decorative metal panels can only be attached if the panel manufacturer is UL listed in UL’s category GVUZ. All installation, sizes and hourly ratings are in accordance with that manufacturers” ...
Installation should be 6" from bottom of the door. See attached templates as reference.  T-5494 for HM Doors W-5494 for Wood Doors
The 3130SE, 4040SE, and the 4040SEH use the same track. The 4040SEL track is longer. The SE/SEH (-3038) track is 22-3/4" long. It functions as a single point hold open, and can be set to h...
Raceway availability: Optional factory installed raceways are available in doors but are not available in frames. Preparation Info: Steelcraft installs a flexible 1/2" ID steel conduit through the...
If a door is being held open by the LCN SEM 7800/1900 magnet or any ME/SE Series Sentronic LCN closer, you can remotely release that door to close by ordering the following parts and wi...
The Von Duprin Guard-X exit device is not fire rated because the deadbolt is not spring loaded. Therefore, there would be no positive latching as required on a fire rated opening. 
Yes, as an option, Steelcraft doors are available with factory prepared for the 98/9949 Concealed Vertical Cable Exit Device. L, B, CE, T and CE-Series doors are available factory prepared Door...
GrainTech® is a Steelcraft door option which provides a wood grained pattern which is embossed into both face sheets of the door. GrainTech doors are factory stained and top coated with a cle...