For most exit devices, please refer to the specific device series catalog for minimum door opening width the device can be cut down to fit.
Be aware that some device options, frame...
Use #18 gauge wire up to 200 feet maximum distance from PS900 x 900-2Q power supply to the QEL exit device. The new QEL+ no longer requires the 900-2Q board but still needs a different option board...
Minimum dimensions to cutouts for glass lights:
Vertical edge of door to edge of cutout = 5 29/32"
Top of door to top of cutout = 6"
Bottom of door to bottom of cutout = 10"
Reinforcing chann...
Yes, glass light can be used or prepped in conjunction with the Von Duprin 94/95 Series INPACT device however there are dimensional limitations between the glass light and the InPact door preparati...
Glass lights available:
Standard Glass Lights - The N4, N5 & V lite can be used at standard locations with out any modification.
Glass Light Options - Other glass lights are available but ...
The ANSI 156.19 standard states (in appendix A-5 Knowing Act Switches) that wall actuators are to have an installation height of a minimum of 34" and a maximum of 48" (center of the switch) of...