What are the wire gauge and length requirements for QEL devices?

Use #18 gauge wire up to 200 feet maximum distance from PS900 x 900-2Q power supply to the QEL exit device. The new QEL+ no longer requires the 900-2Q board but still needs a different option board depending on the applicationĀ nor does it have the same wire run requirements.

QEL+ is the new version of the QEL and uses the same nomenclature, QEL.

QEL+ wire run Lengths

Distance (one way) Wire Gauge
200' 18 AWG
320' 16 AWG
500' 14 AWG
800' 12 AWG