dw frames masonry

RELATED FAQS

Question
Answer
Excessive premature frame rusting is caused by improper jobsite installation practices and most likely caused by the following circumstances: Grout: Frames are grouted in place using incorrec...
F-Series, FN-Series, MU-Series, FE-Series, DE-Series; Grouted Frame
During the construction cycle, spot rust is usually attributed to either material handling damage or improper storage of the material on the jobsite. The material must be repaired and repainted as ...
Mortared Frame; Masonry Frame
CAUTION must be used in investigating this problem - In most cases, excessive field rusting of products is caused by improper storage at the jobsite. That situation must be validated prior to refus...
Mortar; Masonry Frame
FN16, FN14, FN Series; Masonry Frame, Drywall Frame, Conventional Frame
Yes, an additional jamb anchor can be used at the bottom of the frame in lieu of the typical (adjustable or weld-in) base anchor in fire rated frames. This is limited to the anchor designed for...
Conventional Frame, masonry Frame, Drywall Frame, Drywall Slip-on Frame
F16, F14, F12, F Series; Masonry Frame, Drywall Frame, Conventional Frame