double door alk wiring

RELATED FAQS

Question
Answer
The following common wiring diagrams are available:One Single Door with Panic BarElectric Latch Retraction, with Auto OperatorDelayed egress - Fire Rated ApplicationAuto Operator and actuatorElectr...
Electronic Protocols:Access Control Door with electric trimAccess Control with electric strike Access control with electric strike and LCN 4600 automatic operatorAccess Control with remote Loc...
The following anchors are approve for use in FEMA Tornado Resistant openingsMasonry walls:Jamb anchors - Wire masonry anchorsSill (base) anchors - Adjustable base anchorsExisting walls:Jamb an...
Astragals are required on: 3 hour fire rated pairs: Double doors - swinging in the same direction Double Egress - swinging in opposite directions Fire rated Dutch Doors Fire rated 1 3/4" t...
Von Duprin 6223 electric strike is the most common closed back strike or the 6221 for open back strike on inactive leaf that can be used with Schlage L9000 or Von Duprin 7500 mortise lock.
1) Two blinks of the TROUBLE LED means that the AD300 on this channel is not communicating over the RS-485 line. Check wiring connections; verify correct device addressing using HHD/SUS.
2) Three blinks of the TROUBLE LED means that the AD300 on this channel has a Tamper Switch violation. Investigate the lock's Tamper Switch.
3) Five blinks of the TROUBLE LED means that the AD300 on this channel has used cache mode to allow access during a communication loss with the PIB300 or the Access Control Panel.  Press the LINK b...
If your Von Duprin EL (solenoid) device pulls and releases quickly instead of holding the latch retracted, please check all of the items below.In most cases, one or more of these solutions will r...
The Von Duprin 1609 cannot be used on a pair of fire rated doors. We recommend using the Von Duprin fire rated mortise exit device in lieu of the rim device such as the Von Duprin 5575-F, 8875-F or...
Raceway availability: Optional factory installed raceways are available in doors but are not available in frames. Preparation Info: Steelcraft installs a flexible 1/2" ID steel conduit through the...
Ives SB360 surface bolt at top and bottom are the only flush bolts approved for use on H-Series hurricane FBC or NOA applications? The only approved latching hardware for inactive leaf of pairs w...
There are 2 wiring diagrams for sequencing a double door vestibule application shown on page 13 of the 4630/4640 installation instructions.
LCN does offer a 2810 Senior Swing / 2010 manual closer combo for a pair of doors.  Both units contained within the same Senior Swing header. To order a paired operator with a 2810 on&nb...
If a door is being held open by the LCN SEM 7800/1900 magnet or any ME/SE Series Sentronic LCN closer, you can remotely release that door to close by ordering the following parts and wiring per ST ...
Chexit devices shipped after 8-24-2015 with motor driven:Attached is the installation instructions of the the Von Duprin Chexit devices that includes the wiring diagrams.Installation Instructions&n...
Chexit devices shipped before 8-24-2015 with solenoid driven:Attached are the single and double door wiring , cable voltage reading documents for trouble shooting, and the installation in...
Senior Swing Power Operators
The following may cause the ALK to go into alarm: Make sure red and blue wires on the RX switch are connected to the exit alarm ALK terminal block and yellow wire is taped off. Check the red an...
Clear Opening Width for swinging doors is measured (with the door open 90 degree) from the face of door to stop soffit on strike jamb.          &nbs...
The overhead concealed operators (2850/2860) will not work on a Double Egress frame because the doors are not in the same plane. You will have to use the surface mount (9553 / 9563) on Double Egres...
Followings are the reason for 98/99 exit alarm ALK not sound when push bar is activated. Make sure key switch on exit alarm ALK is turned on, wait for 20 seconds before you activating the pushba...
The 4040SE uses the regular arm for any Push Side mounting (minimum 28" door width). ST-2788 (a special arm and track) can be used to mount a 4040SE on the Push Side of a smaller (narrow) door. Sm...
The minimum door opening width (for mounting a pair of 4640 or 4630 operators on a double door) is 72" wide (2 - 36" door leaves). Mounting the 4640 or 4630 on a double door that is less than 72" w...
Standard exit alarm ALK devices are available with cylinder dogging option as of October, 2011. The device can be ordered standard with cylinder dogging and exit alarm ALK option on non fire rat...
Yes, wood doors can be used and installed in most hollow metal frame applications including FE-Series and DE-Series Double Egress frames. Caution - For fire rated applications the wood door manufa...
Surface Mounting - A 9542 DD (double door) header and a 9540-18 mounting plate can be used on the active leaf. A manual closer with a PA (parallel arm) can the be installed on the inactive leaf.  B...
If the green terminal block has been broken off of the exit alarm ALK you must replace the exit alarm ALK PC board part number 101030-00.
Schlage offers the AL170 single dummy trim, but for applications where a double dummy is needed you can install two AL170 dummy trims back-to-back.  Each AL170 is shipped with a threaded rod (part ...
The 5100 strike details are listed below: Only operates with 12VDC or 24VDC power supply. Will not operate with AC transformer. 12 or 24VAC can be converted to 12/24VDC using Von Duprin SO12 o...
All new 22, 33/35A and 98/99 series exit devices with exit alarm ALK option can be hard wired to the PS902 power supply as a standard  feature.
Schlage and Falcon double cylinder deadbolts have concealed screws to prevent tampering. The two methods used to conceal the thru-bolts are using screw caps or a faceplate. Use the below instructio...
The standard Falcon 25V vertical rod cannot be cut to fit on a 2 feet door opening.This device requires 2' 7 1/8" minimum door opening. Falcon offers a device that can be used on a 2 feet door...
The Falcon W12 single dummy lock cannot be mounted back-to-back to create a double dummy.  There is no access to surface mount the screws and the lever is held in place by a roll pin wh...
A fire rated door for 3 hours can have one glass light maximum: 100 square inches and must have an approved glass (Firelite type) Max glass size cannot exceed 12" in width or 33" in height. Wi...
The backset for a 98/99 rim PANIC device with 1609 strike is 2 3/8" from center of the opening to center line of the device. See template