does chexit rearm on its own aftr fire alarm

RELATED FAQS

Question
Answer
Fire alarm contact would tie right into the Von Duprin Chexit device not to the PS914 power supply. There is no requirement to install the fire alarm board.
If a door position switch (DPS) is connected across the green and white wires of the CX the CX would go into alarm if the door is held open when it attempts to rearm.  If no DPS is used the ...
Chexit devices shipped after 8-24-2015 with motor driven:If two pin REX connector cable is plugged into the Chexit module and Module REX LED is OFF, the RX switch is defective and needs to be repla...
Chexit devices shipped prior to 8-24-2015 with solenoid driven:If Chexit device goes into alarm with fast flashing red LED after the rearm time, the RX switch may be out of adjustment or defective....
A Door Position Switch is a switch and magnet mounted on the door and frame that monitors the door status. If door is held open beyond rearm time or if door is forced open, alarm wil...
The Von Duprin Chexit device will not automatically rearm itself after a fire alarm clears.  After a Fire Alarm has triggered the Von Duprin Chexit device, the device must be manually reset&nb...
Followings could cause the Chexit device to go into alarm after the rearm time: Chexit devices shipped after 8-24-2015 with motor driven: Module DPS LED is ON DPS switch contact is open: Close t...
Chexit devices shipped prior to 8-24-2015 with solenoid driven: Chexit device has a RX switch with a connector that needs to be connected to the Chexit module otherwise the alarm will sound af...
Chexit devices shipped prior to 8-24-2015 with solenoid - the solenoid pulls and drops, the alarm sounds, there is a solid LED or no LED light after the rearm t...
Chexit devices shipped with motor after 8-24-2015. 1. When Chexit device is set for more than zero second rearm time (factory setting is 10 second rearm time) and device goes into alarm immediatel...
Chexit devices shipped with solenoid prior to 8-24-2015. 1.  When Chexit device  is set for more than zero second rearm time (factory setting is 10 second rearm time) and device goes...