Is the Von Duprin Chexit part number 050228 a module or a kit?
Resolution:
The circuit board is sometimes referred to as a "module" in the field.:
Can a Chexit release delay time be changed in the field?
Resolution:
The release delay time for the Chexit is programmed into the Chexit module and cannot be changed in the field.The ability to change the delay time is restricted by the UL listing of the device.&nbs...:
What would cause the Von Duprin Chexit device to have one red flash when armed then nothing?
Resolution:
Chexit devices shipped prior to 8-24-2015 with solenoid driven. The GREEN wire is not shorted to the WHITE if no Access Control system is used.If Access Control system is used,...:
How do you test the potted circuit breaker or potted module on an EL device?
Resolution:
For Potted Modules (black color) shipped before August of 2012, you can test by applying power to the potted circuit breaker to and if good the following voltages will be seen (be careful...:
What is the Von Duprin Chexit module part number?
Resolution:
Part number for Von Duprin standard 15 sec. release Chexit module shipped after 8-24-2015 with motor driven is 040086-00. Part number for Von Duprin standard 15 sec. release Chexit module shi...:
How to test the RX switch in a Chexit device.
Resolution:
Chexit devices shipped prior to 8-24-2015 with solenoid driven: If Chexit device goes into alarm with fast flashing red LED after the rearm time, the RX switch may be out of adjustment or defect...:
Solenoid on Chexit pulls back and immediately lets go and alarm goes off with red solid light.
Resolution:
The following could cause the Chexit solenoid ( devices shipped prior to 8-24-2015) pulls in then drop out with no alarm. Mechanical adjustment such as vertical rods. Disconnect t...:
What would cause the Von Duprin delay egress Chexit device not to provide delay egress?
Resolution:
For Solenoid driven Chexit devices shipped from the factory prior to 8-24-2015, the following could cause the device not to provide delay egress:Measure the voltage between green and orange wires o...: