Chexit light flashes once

RELATED FAQS

Question
Answer
Most common issue listed below: Chexit devices shipped after 8-24-2015 with motor driven. The Green wire is not shoeted to the Red wire if no Access Control system is used.If Access Control is us...
 Chexit devices shipped prior to 8-24-2015 with solenoid driven. The GREEN wire is not shorted to the WHITE if no Access Control system is used.If Access Control system is used,...
The following could cause the Von Duprin CX solenoid ( devices shipped prior to 8-24-2015) to pull and drop and sound the alarm with solid LED light. Wrong power supply, requires Von Duprin ...
The following could cause the Chexit solenoid ( devices shipped prior to 8-24-2015) pulls in then drop out with no alarm. Mechanical adjustment such as vertical rods. Disconnect t...
If Chexit device LED blink once when you turn the unit on, the External inhibit green wire is not by passed or not connected to the access control normally closed contact.  For devices sh...
Inadequate power or wrong gauge wire is used the inrush current demand by CX will overload and shutdown the power supply.  You must use the Von Duprin PS873 or newer PS914 supply.   Related soluti...
Chexit devices shipped prior to 8-24-2015 with solenoid driven could cause the Von Duprin CX solenoid to pull and drop and sound the alarm with solid LED or no LED light after the rear...
Followings could cause the Chexit device to go into alarm after the rearm time: Chexit devices shipped after 8-24-2015 with motor driven: Module DPS LED is ON DPS switch contact is open: Close t...
Chexit devices shipped prior to 8-24-2015 with solenoid driven: Chexit device has a RX switch with a connector that needs to be connected to the Chexit module otherwise the alarm will sound af...
A red and green flashing LED's on a QEL indicates the device has been tampered with while power was applied, the push pad was pulled out at least three time. Wait 15 seconds and latchbolt will retr...
The push bar being pulled out three times while power is applied causes the lights to flash and the device to stop retracting.
Check to make sure there is no bind of the latch.
Devices were shipped from the factory with motor driven after 8-24-2015. First confirm that you are using PS900 series (902,904,906 or 914) power supply.      1. Mea...
Devices were shipped from the factory with solenoid driven prior to 8-24-2015.  First confirm that you are using a PS873 or PS914 power supply.Measure the DC voltage at the ten wire hardness a...
Many problems with AD-series locks can be resolved by performing a Factory Default Reset (FDR).  This process will clear the memory and any stored configurations, re-enabling default...
To perform an FDR on an AD-series lock: 1.     Remove the inside top cover of the lock.  This will expose the main board and activate the tamper switch.   2. &...
Note: An FDR cannot be performed if an HHD is plugged into the lock.