chexit does not power up

RELATED FAQS

Question
Answer
For devices shipped after 8-24-2015 with motor driven:  a.       0-200 ft, use  #18 gauge wire b.      0-500 ft, use #14 g...
For Product Shipped prior to 8-24-2015 with solenoid and EPT or Door Loops:           a.       0-100 ft, use #14 Gauge Wire ...
The following could cause the Von Duprin CX solenoid ( devices shipped prior to 8-24-2015) to pull and drop and sound the alarm with solid LED light. Wrong power supply, requires Von Duprin ...
The following could cause the Chexit solenoid ( devices shipped prior to 8-24-2015) pulls in then drop out with no alarm. Mechanical adjustment such as vertical rods. Disconnect t...
If the Chexit device shipped prior to 8-24-2015  is not adjusted correctly ( Check vertical rod or Mortise finger) without using the door position switch and nuisance delay is&n...
 
When a CX99L-BE is not armed the exterior 996L BE lever trim will be free to retract the CX latch for entrance.  When the CX99-L BE is armed the exterior 996L BE lever will not move and...
For Motor driven Chexit devices shipped from the factory after 8-24-2015, the Chexit Secure Relay Contacts( white and violet wires) change state to signal the device is not secure. Check the f...
For Solenoid driven Chexit devices shipped from the factory prior to 8-24-2015, the following could cause the device not to provide delay egress:Measure the voltage between green and orange wires o...
Devices were shipped from the factory with motor driven after 8-24-2015. First confirm that you are using PS900 series (902,904,906 or 914) power supply.      1. Mea...
Devices were shipped from the factory with solenoid driven prior to 8-24-2015.  First confirm that you are using a PS873 or PS914 power supply.Measure the DC voltage at the ten wire hardness a...
If Chexit device LED blink once when you turn the unit on, the External inhibit green wire is not by passed or not connected to the access control normally closed contact.  For devices sh...