chexit device with be function alarms

RELATED FAQS

Question
Answer
Followings could cause the Chexit device to go into alarm after the rearm time: Chexit devices shipped after 8-24-2015 with motor driven: Module DPS LED is ON DPS switch contact is open: Close t...
Chexit devices shipped prior to 8-24-2015 with solenoid driven: Chexit device has a RX switch with a connector that needs to be connected to the Chexit module otherwise the alarm will sound af...
The Chexit device has a different base plate and center case than the ALK.  The Chexit device would need to be replaced with an ALK device.
For Motor driven Chexit devices shipped from the factory after 8-24-2015, the Chexit Secure Relay Contacts( white and violet wires) change state to signal the device is not secure. Check the f...
For Solenoid driven Chexit devices shipped from the factory prior to 8-24-2015, the following could cause the device not to provide delay egress:Measure the voltage between green and orange wires o...
Chexit devices shipped with motor after 8-24-2015. 1. When Chexit device is set for more than zero second rearm time (factory setting is 10 second rearm time) and device goes into alarm immediatel...
Chexit devices shipped with solenoid prior to 8-24-2015. 1.  When Chexit device  is set for more than zero second rearm time (factory setting is 10 second rearm time) and device goes...
To get a dry contact signal from a Chexit device to monitor the alarm, use the blue and brown wires (do not connect the blue to the red)  of the harness connector cable tha...
If the Chexit device shipped prior to 8-24-2015  is not adjusted correctly ( Check vertical rod or Mortise finger) without using the door position switch and nuisance delay is&n...
 
The Von Duprin Chexit device will not automatically rearm itself after a fire alarm clears.  After a Fire Alarm has triggered the Von Duprin Chexit device, the device must be manually reset&nb...
The following could cause the Chexit device shipped prior to 8-24-2015 with solenoid driven to go into weak alarm with solid LED light: Wrong power supply- Chexit device requires  a...
The Von Duprin Chexit-BOCA has special software. Following is the function of this software: When Chexit device push bar is pushed and goes into alarm it will release in 15/30 sec...