can RX and cx
”
RELATED FAQS
Question
Answer
What is the part number for the CX-RX switch?
Resolution:
For solenoid driven Chexit devices shipped from the factory prior to 8-24-2015, the RX switch is no longer available. This part was discontinued in 2019.If the older version Chexit RX switch ...:
Is there a template that shows where to drill the hole for E/EL/SS/RX/LX/CX wires?
Resolution:
The hole should be drilled in the field once the end cap is located on the door. It is a 5/8" hole, that is located 5/16" from the end of the mechanism case. See installation instruction of t...:
Can you have a RX and CX in the same device?
Resolution:
The CX device has an internal RX switch that is wired to the CX circuit board. This RX switch is not available to outside monitoring and no other RX switches may be added to the CX device. :
How to test the RX switch in a Chexit device.
Resolution:
Chexit devices shipped prior to 8-24-2015 with solenoid driven: If Chexit device goes into alarm with fast flashing red LED after the rearm time, the RX switch may be out of adjustment or defect...:
Who can adjust or replace the Chexit RX switch?
Resolution:
For Chexit devices with solenoid driven shipped from the factory prior to 8-24-2015, the RX switch is ordered as a "Special CX RX Switch". It may only be installed or adjusted ...:
Chexit goes into alarm with fast flashing LED and not locking after rearm time.
Resolution:
Chexit devices shipped prior to 8-24-2015 with solenoid driven: Chexit device has a RX switch with a connector that needs to be connected to the Chexit module otherwise the alarm will sound af...:
Von Duprin Chexit device keeps going into alarm by itself.
Resolution:
Chexit devices shipped with solenoid prior to 8-24-2015. 1. When Chexit device is set for more than zero second rearm time (factory setting is 10 second rearm time) and device goes...: