can ada operator power electric strike

RELATED FAQS

Question
Answer
The 8200 Series operator CANNOT power a strike, maglock, or EL device. A separate power supply is ALWAYS required. There is an onboard relay to control a strike, maglock, or EL device.
The 4630/4630 operator has a 12 VDC and 24 VDC output that can power an electric strike or maglock. The wiring diagrams are shown on page 14 of the installation instructions (attached). 4600 Insta...
The 4600 Series operator has both a 12VDC and 24VDC output rated at 1A (combined load) to power strikes, maglocks, and other devices, but an EL device "always" has to have a separate PS914-2RS Seri...
The Benchmark III control has a 24VDC, 2.5 amp power supply, and built in relay for controlling electric strikes or other accessories less than 2.5 amps current load. For a fail secure strike, r...
You can't run 24VDC into the 12VDC electric strike, over voltage such as this will cause the solenoid to heat up and damage the solenoid.  You must change to a 24V solenoid, part number 050240-00.
Option boards are not required with PS900 series power supplies when using electric strikes. See the list of options below. The PS902 would power up to 5 electric strikes at 24VDC or&n...
The power supply output in the 7900 series control box is a 12VDC output, rated at (1/4A) 0.250A. It cannot be used to power a strike or maglock. You need to have a separate power supply for the st...
An electric strike or maglock (24 volt only) can be wired to a Senior Swing 2800/9500 series operator using the P10 Lock Interface cable. To power the 24VDC electric strike or maglock off a LCN Se...
Electrical hinges or a power transfer units are the most commonly used practices to run electric power to locks and/or strikes. Electric Hinges: Most electric hinges will fit into...