Question
Answer
How do you wire an electric strike to a 4600 Series operator?
Resolution:
The 4630/4630 operator has a 12 VDC and 24 VDC output that can power an electric strike or maglock. The wiring diagrams are shown on page 14 of the installation instructions (attached). 4600 Insta...:
Can the 8200 Series operator power a electric strike?
Resolution:
The 8200 Series operator CANNOT power a strike, maglock, or EL device. A separate power supply is ALWAYS required. There is an onboard relay to control a strike, maglock, or EL device.:
Can you operate a Doromatic EL 1490 with an LCN power supply?
Resolution:
This is not possible. Due to the device's 16 Amp in-rush it would require it's own PS914-2RS which will power 1 or 2 devices.:
What is the power output of a 4600 operator?
Resolution:
The 4600 Series operator has both a 12VDC and 24VDC output rated at 1A (combined load) to power strikes, maglocks, and other devices, but an EL device "always" has to have a separate PS914-2RS Seri...:
Will the 9100 series Benchmark III power an electric strike?
Resolution:
The Benchmark III control has a 24VDC, 2.5 amp power supply, and built in relay for controlling electric strikes or other accessories less than 2.5 amps current load. For a fail secure strike, r...:
Can 24 volts be run to a 12 volt 6000 series electric strike solenoid?
Resolution:
You can't run 24VDC into the 12VDC electric strike, over voltage such as this will cause the solenoid to heat up and damage the solenoid. You must change to a 24V solenoid, part number 050240-00.:
Can you power a electric strike from the 7900 control boxes?
Resolution:
The power supply output in the 7900 series control box is a 12VDC output, rated at (1/4A) 0.250A. It cannot be used to power a strike or maglock. You need to have a separate power supply for the st...:
What power supply is required to operate the 6000 series electric strike?
Resolution:
Option boards are not required with PS900 series power supplies when using electric strikes. See the list of options below. The PS902 would power up to 5 electric strikes at 24VDC or&n...:
Can you power an electric strike or maglock from the 9500 Series Senior Swing?
Resolution:
An electric strike or maglock (24 volt only) can be wired to a Senior Swing 2800/9500 series operator using the P10 Lock Interface cable.For Current Sr Swing control boxes with ID# 72940 on th...:
What is the most common practice for running electric power from a frame to the door and hardware?
Resolution:
Electrical hinges or a power transfer units are the most commonly used practices to run electric power to locks and/or strikes. Electric Hinges: Most electric hinges will fit into...: