On fire rated transom and/or sidelight frames and fire rated window frames, Steelcraft labeling procedures only control the O/A width and/or height of the frames based on wall condition. The amount...
The following size limitations per frame unit, are in enforced for welded elevation frames shipped from the factory. These limitations are in place due to the physical size of shipping tr...
Steelcraft offers all the standard lights as well as special size glass lights in the H-series door. Effective April 1, 2012, (Bulletin # B-100.12) the default for Dezigner Trim in H-Series Doors...
When dealing with glass lights in doors, there are three (3) critical dimensions which must be coordinated: Exposed Glass Size (EGS) - the horizontal and/or vertical dimensional size of the vision...
Maximum glass light sizes for 3 hour fire doors is as follows: Wire glass - not approved for use in 3 hour fire doors. Ceramic glass: UL & ITS/WH allow one (1) light with 100 square inc...
The GCS (Glass Cutting Size) is determined by adding 1 1/4" to EGS (Exposed Glass Size) to both the height and width dimensions. Ex: EGS = 20" w. x 30" h. GCS = 21 1/4" wide x 31 1/4" high St...
Maximum glass light size for a 90 minute (1 1/2 hour) door depends on the type of glass being installed. Wire glass = 100 square inches is max exposed glass when wire glass is used. Note - ma...
Minimum dimensions to cutouts for glass lights: Vertical edge of door to edge of cutout = 5 29/32" Top of door to top of cutout = 6" Bottom of door to bottom of cutout = 10" Reinforcing chann...
Yes. 1 7/16" thick glass but a special rabbet size is required. The size of rabbet required for the frames would depend on the size of the glazing bead being used. For 1" wide glazing stops, ...
DW-Series Fire Rated Borrowed Lights are available in the following sizes: 60 minute (1 hour) rating = 2721 square inches of visible glass. maximum frame rabbet to rabbet dimensions = 78 1/4...