what power supply for QEL with automatic operator
”
RELATED FAQS
Question
Answer
What power supply do I need for my 2 QELA devices with LCN auto operator?
Resolution:
Use the PS902-2RS power supply with LCN auto operator on single door, PS904-2RS power supply on double door and PS904/906-2RS-2RS for 2 pair of QELA is required for basic operation with a...:
What power supply is required for two EL devices and one LCN auto operator?
Resolution:
Von Duprin PS914 x 900-4RL supports two EL with two auto operator.:
Will the Von Duprin PS902 power supply operate the QEL device?
Resolution:
The Von Duprin PS902 power supply will operate the QEL device as long as you also use the 900-2Q board for devices shipped prior to September of 2012. After July of 2012, the 900-2RS boa...:
How many Von Duprin QEL devices can be connected to a power supply?
Resolution:
Product Ordered before 7/10/2012 - Product identified by no label on QEL motor. You must use the 900-2Q option board with the PS900 power supplies to operate the QEL devices. The attached ta...:
What is the power output of a 4600 operator?
Resolution:
The 4600 Series operator has both a 12VDC and 24VDC output rated at 1A (combined load) to power strikes, maglocks, and other devices, but an EL device "always" has to have a separate PS914-2RS Seri...:
What are the power requirements of the 4600 series operator?
Resolution:
The 4600 series operator requires a 120 VAC @ 1.5 Amp power input to be field connected. Hardwiring is always recommended, but a "plug-in" line cord can be installed (by others) with the proper cor...:
What is the input / output of the 8200 series operator?
Resolution:
The Falcon 8200 series operator requires a input of 120 VAC @ 1 Amp.:
What are Pneumatic Automatic Operators?
Resolution:
Pneumatic Automatic Operators are used in areas where electrically operated devices are not convenient or permitted. Consists of a modified, heavy-duty door closer for manual oper...:
What are Electro-hydraulic Automatic Operators?
Resolution:
Electro-hydraulic Automatic Operators are: Designed for manual opening applications where there is occasional need for automating the door to meet ADA requirements. Electrically powere...:
Does the QEL retract the latch bolt and the pushpad?
Resolution:
Yes the Von Duprin QEL exit device retracts the latch bolt and pushpad. Pushpad and latch bolt stay retracted as long as power is applied to the QEL exit device. :
Will the MPB-842 or MPB-840 power EL or QEL devices?
Resolution:
The old MPB842 power supply will power up to two EL electric panic bars but will not power the QEL devices. A defective potted module inside the electric panic bar or defective power supply coul...:
Can I run 4 QEL devices from one PS902?
Resolution:
No, you can only add one 900-2Q option board to the PS902 power supply and 900-2Q only can support two QEL devices.:
Can you operate a Doromatic EL 1490 with an LCN power supply?
Resolution:
This is not possible. Due to the device's 16 Amp in-rush it would require it's own PS914-2RS which will power 1 or 2 devices.:
Why does the auto operator not open the door when installed with a Chexit?
Resolution:
Chexits are NOT electric latch retraction devices, therefore the latch will not retract and allow the opener to swing the door open. Chexits block and unblock the latch. In order for a Ch...:
Can a Senior Swing 2850 or 2860 be used on a Double Egress (DE) door?
Resolution:
The overhead concealed operators (2850/2860) will not work on a Double Egress frame because the doors are not in the same plane. You will have to use the surface mount (9553 / 9563) on Double Egres...:
What power operator is recommended/used for occasional activation with mainly manual traffic?
Resolution:
The 4630/4640 Series operator is designed/recommended for a door that will see mostly manual traffic with the occasion automatic/ handicap operation.:
Is the 871-2Q board required on QEL devices when using the PS 873 AO to operate my QEL devices?
Resolution:
The QEL exit devices that were shipped prior to August, 2012 will only communicate to the PS873 with 871-2Q option board or PS900 series with 900-2Q option board. If you...:
What is power boost on a Senior Swing or Benchmark operator?
Resolution:
Power Boost is a positive latching feature that increases the latch force, to over come building stack pressure or door weather stripping, etc, if the door stops before co...:
Can an auto operator be installed on a Dutch door?
Resolution:
Yes, an automatic operator can be installed on a Dutch door. The operator must be installed on the top leaf of the Dutch door. Only the top half will open unless the top and bottom leaves (se...:
What is the power output on the Senior Swing 9500 series?
Resolution:
Below information is for the 120v Sr Swing Operators.For Sr Swing digital Control Boxes made from 2006 to Dec. 9th 2019 the Senior Swing operator had a 24VAC output , rated at 1.5 Am...:
What is the difference between the Senior Swing 9540 and 9530 Series power operators?
Resolution:
The 9542 is the single door operator that mounts on the "push side" of the opening with a REG arm. The 9531 is the single door operator that mounts on the "pull side" of the opening with a STD arm...:
What are ElectroMechanical Automatic Operators?
Resolution:
ElectroMechanical Automatic Operators are designed to automatically open when activated. The Benchmark Series are Medium Duty "Commercial" automatic operators, often used on of...:
How do I program my device?
Resolution:
The programming processes for Allegion devices can be both product and features specific. Some products programming processes are electronic in nature, others are physical in nature. &nb...:
What operator is best for high traffic automatic use.
Resolution:
The Senior Swing 9500 or 2800 series operator is designed to for "High Traffic - High Abuse" areas.:
Can the 4630/4640 cylinder only be replaced?
Resolution:
The 4040(XP) door closer can be used as a temporary replacement in a 4630/4640 operator to provide manual control of the door while the 4630/4640 closer cylinder is being repaired or a replacement ...:
What would cause a Senior Swing to open too far?
Resolution:
The Senior Swing operator is designed to power open the door to 90°. The built in dead stop (in the gearbox) prevents it from opening any further. If the Senior Swing operator is opening to far (pa...:
Why would a Falcon 8200 Series operator be blowing the fuse?
Resolution:
If the Main AC fuse is blowing, the control box is defective and needs to be replaced. The "Main Fuse" is a (5x20MM) 1 Amp Slow Blow fuse. If the 12VAC fuse is blowing, verify they are not trying...: