Allegion
Terms of Use
Privacy Policy
Frequently Asked Questions
Ask your question
Entering your question as a complete sentence will provide more accurate results than keywords or phrases.
User questions
FAQs
Category List
“
operator power electronic lock
”
RELATED FAQS
Question
Answer
Can the 8200 Series operator power a electric strike?
Resolution:
The 8200 Series operator CANNOT power a strike, maglock, or EL device. A separate power supply is ALWAYS required. There is an onboard relay to control a strike, maglock, or EL device.:
What is the power output of a 4600 operator?
Resolution:
The 4600 Series operator has both a 12VDC and 24VDC output rated at 1A (combined load) to power strikes, maglocks, and other devices, but an EL device "always" has to have a separate PS914-2RS Seri...:
How do you wire an electric strike to a 4600 Series operator?
Resolution:
The 4630/4630 operator has a 12 VDC and 24 VDC output that can power an electric strike or maglock. The wiring diagrams are shown on page 14 of the installation instructions (attached). 4600 Insta...:
Can you operate a Doromatic EL 1490 with an LCN power supply?
Resolution:
This is not possible. Due to the device's 16 Amp in-rush it would require it's own PS914-2RS which will power 1 or 2 devices.:
Why would an LCN 8310-865 RF Receiver have a flashing "RED" light?
Resolution:
When the "RED" LED on the 8310-865 RF Receiver is blinking, it is receiving an RF signal (interference) from a non programmed device. When receiving this type of signal, it will not ...:
What is the power draw of a Senior Swing series operator?
Resolution:
The Senior Swing (2800/9500) Series operator has a 120VAC @ 2.5 Amp current draw for a single door (2811/9531/9542) or simultaneous pair(2853/9553). The independent pair units (2863/...:
What power supply is needed for EL devices?
Resolution:
You can use a Von Duprin PS914 power supply with any of the following option boards depending on the application. 900-2RS board will power 1 or 2 devices that do not require timing from pow...:
Does the 9540 Senior Swing need a separate relay board for wiring to electric locks?
Resolution:
The Senior Swing control box has a built in (programmable) relay output for connection to a Fail Safe/Fail Secure electric strike/maglock or to an EL Device power supply.:
How do I program my device?
Resolution:
The programming processes for Allegion devices can be both product and features specific. Some products programming processes are electronic in nature, others are physical in nature. &nb...: