Are astragals required on fire doors?
Resolution:
Astragals are required on: 3 hour fire rated pairs: Double doors - swinging in the same direction Double Egress - swinging in opposite directions Fire rated Dutch Doors Fire rated 1 3/4" t...:
Can a Senior Swing 2850 or 2860 be used on a Double Egress (DE) door?
Resolution:
The overhead concealed operators (2850/2860) will not work on a Double Egress frame because the doors are not in the same plane. You will have to use the surface mount (9553 / 9563) on Double Egres...:
Can wood doors be used with with double egress frames?
Resolution:
Yes, wood doors can be used and installed in most hollow metal frame applications including FE-Series and DE-Series Double Egress frames. Caution - For fire rated applications the wood door manufa...:
Do you need Double Egress arm to install a 4040SE on the Push Side of a door?
Resolution:
The 4040SE uses the regular arm for any Push Side mounting (minimum 28" door width). ST-2788 (a special arm and track) can be used to mount a 4040SE on the Push Side of a smaller (narrow) door. Sm...:
DOUBLE EGRESS DOORS
Resolution:
; two way corridor openings:
Can a Von Duprin delay egress controller DE5101 run a pair of doors?
Resolution:
One Delayed Egress Controller (DE5101) can run two mag locks on a pair of doors, provided the doors are not controlled independently:
What is the maximum size of a UL fire rated three (3) sided frame?
Resolution:
Fire Rated three (3) frames are available in the following maximum door opening sizes: F and FN-Series frame:4' 0" X 10' 0" single door opening8' 0" X 10' 0” double door openingMU-Series frame...:
What is an astragal?
Resolution:
An Astragal is an applied molding attached most commonly to the meeting edge of doors to: Protection against weather conditions Minimize the passage of light between the doors Retard the passa...:
What is the difference between the FE and DE-Series frames
Resolution:
A Double Egress frame is a double door frame prepared to receive two single-acting doors swinging in opposite directions (both doors are) the same hand. These openings are installed in cross corrid...:
What astragals are available?
Resolution:
Types of astragal offered from Steelcraft are as follows: "Z" Astragal - For information on "Z" astragal types and attachment refer to the TD Manual page 3.3.17. Most commonly used on double ...:
What is the definition of double egress?
Resolution:
Double Egress Opening: A pair of swinging doors, each leaf which swings in the opposite direction of the other. DOORS: A pair of doors swinging in opposite directions without a vertical mullion....:
Is there a mullion for use in double egress applications?
Resolution:
There is no mullion for double egress openings. Mullions only applies to the doors that open in the same direction.:
Will CX re-arm if door is held open?
Resolution:
If a door position switch (DPS) is connected across the green and white wires of the old CX (green and red of new CX) the CX would go into alarm if the door is held open when it attempts to rearm.&...:
What are the minimum header lengths for a Senior Swing?
Resolution:
The minimum header lengths for a Senior Swing with standard Spindle centers are:Concealed 2810 Series:2811 single door (offset pivot or butt hinge) -- 33".2811 single door with stop (cent...:
Does a SEH require a door closer?
Resolution:
The SEH is an "electronic holder" (ONLY) that is used to hold open a Fire Rated opening. It requires a door closer to be mounted on the opposite side. It is normally used on an existing opening wit...:
Do Von Duprin Exit devices meet the 5 pound force requirement for opening an ADA handicapped door opening?
Resolution:
The 5 pound force requirement is in reference to the maximum force to swing the door, not the maximum force allowed to unlatch the exit device. Maximum allowed force to retract the Von D...:
Outside lever on the T and RU 571's won't unlock after egress.
Resolution:
Replace the lock chassis as necessary for any T locks exhibiting this issue. RU locks need to be replaced entirely. :
Why does the ND40 stay locked after egress?
Resolution:
There is potential for ND40/ND44's manufactured around March 2011 to remain locked after egress, or after the latch is depressed. There was an issue with the keycam that created a bind when l...:
What is a 4430 / 4330?
Resolution:
The 4330 / 4430 is an obsolete ME closer replaced by the 4310ME or 4410ME Series.:
What are Hold Open Closers & Magnets?
Resolution:
Hold Open Closers & Magnets (Fire/Life safety products) provide a wide range of solutions. Single or multi-point hold open closers Utilize an electromechanical closer. Hold the door o...:
Can I use a Glynn Johnson 410 with a 4040 regular (pull side) mount?
Resolution:
ST-1630 is required when mounting a 4041 or 4040XP door closer regular (pull/hinge) side with a concealed GJ100 or GJ410 series over head stop.:
DOOR HOLDER
Resolution:
hardware; Suface Holder, Concealed Holder, Over Head Stop: