Handicap door not opening with push pad

RELATED FAQS

Question
Answer
The standard Falcon 25V vertical rod cannot be cut to fit on a 2 feet door opening.This device requires 2' 7 1/8" minimum door opening. Falcon offers a device that can be used on a 2 feet door...
If a 4600 clicks, but won't open the door: Verify proper connection of all the control box connectors. Verify correct manual operation of door. Verify actuator connections and any strike/maglo...
The 5 pound force requirement is in reference to the maximum force to swing the door, not the maximum force allowed to unlatch the exit device.  Maximum allowed force to retract the Von D...
The ANSI 156.19 standard states (in appendix A-5 Knowing Act Switches) that wall actuators are to have an installation height of a minimum of 34" and a maximum of 48" (center of the switch) of...
  Pushing on the push  bar or activating the EL/QEL or the trim on Von Duprin XP98/99 exit device does not retract the latch, it releases the latch only. Door must be pushed or pulled when device o...
If the Chexit device shipped prior to 8-24-2015  is not adjusted correctly ( Check vertical rod or Mortise finger) without using the door position switch and nuisance delay is&n...
 
The 4630/4640 Series operator is designed/recommended for a door that will see mostly manual traffic with the occasion automatic/ handicap operation.