What is the ANSI recommendation for the distance between the actuator and the door opening?

Always check the most current revision of the ANSI A156.19 standard for recommendation or requirement of the location of a Knowing Act switch.

2019 ANSI A156.19 states the requirement of the Knowing Act Switch Location as follows:

When a knowing act switch is used: it shall be installed in a location within view of the door; have an installation height of a minimum of 34 in. and a maximum of 48 in., or as specified by the local building codes; shall remain accessible from the swing side when the door is opened; and shall not be located in a position where the user would be in the path of the moving door. If located seven feet or more from the center of the door, there shall be an additional time delay of two seconds for each additional foot.


DISCLAIMER:

INFORMATION PROVIDED THROUGH THIS SITE IS PROVIDED TO YOU AS IS WITHOUT ANY EXPRESS REPRESENTATIONS OR WARRANTIES OF ANY KIND, AND WE MAKE NO REPRESENTATION OR WARRANTY THAT THIS SITE(OR ANY INFORMATION PROVIDED IN RESPONSE TO YOUR INQUIRY), WILL BE ACCURATE, COMPLETE, OR ERROR-FREE.

YOU AGREE THAT YOU MUST EVALUATE ALL INFORMATION AND RESPONSES, AND THAT YOU BEAR ALL RISKS ASSOCIATED WITH, THE USE OF THIS SITE, INCLUDING ANY RELIANCE ON THE ACCURACY,COMPLETENESS, OR USEFULNESS OF ANY INFORMATION OR MATERIALS MADE AVAILABLE THROUGH THIS SITE.

Other users ask