Allegion
Terms of Use
Privacy Policy
Frequently Asked Questions
Ask your question
Entering your question as a complete sentence will provide more accurate results than keywords or phrases.
User questions
FAQs
Category List
“
wire gauges for qel
”
RELATED FAQS
Question
Answer
How many Von Duprin QEL devices can be connected to a power supply?
Resolution:
Product Ordered before 7/10/2012 - Product identified by no label on QEL motor. You must use the 900-2Q option board with the PS900 power supplies to operate the QEL devices. The attached ta...:
What are the wire gauge and length requirements for QEL devices?
Resolution:
Use #18 gauge wire up to 200 feet maximum distance from PS900 x 900-2Q power supply to the QEL exit device. The new QEL+ no longer requires the 900-2Q board but still needs a different option board...:
Why would QEL retract and release repeatedly?
Resolution:
The following could cause the QEL device to retract and release repeatedly: If this is a vertical rod type device, the vertical rods could be adjusted too short. Check rods for dead locking, ...:
What size wire and run is recommended when using a PS914-2RS?
Resolution:
For Product Shipped Prior to August 2012 using the old (black) potted module:a. 0-100 ft 14 gauge wireb. 0-200 ft 12 gauge wire&nbs...:
What is the difference between the EPT 2 and the EPT 10?:
Resolution:
The EPT2 has (2) 18 gauge wires and the EPT10 has (10) 24 gauge wires. Even though they are 18 gauge or 24 gauge wires they are special high stress, high flex, & high current wires specifically u...:
What is the maximum distance you can wire a PIB300 or PIB301 from a Access Control Panel?
Resolution:
See the User Guide instructions in the links below:
Why is my Von Duprin CX going into a weak alarm after the rearm delay?
Resolution:
Chexit devices shipped prior to 8-24-2015 with solenoid - the solenoid pulls and drops, the alarm sounds, there is a solid LED or no LED light after the rearm t...: