wire gauge for von duprin el device
”
RELATED FAQS
Question
Answer
What gauge wire is needed for CX red and black power wires?
Resolution:
For Product Shipped prior to 8-24-2015 with solenoid and EPT or Door Loops: a. 0-100 ft, use #14 Gauge Wire ...:
What wire gauge and run is recommended for Von Duprin electric latch retraction EL device?
Resolution:
:
Why is the Von Duprin PS873 power supply buzzing or chattering?
Resolution:
Some transformers in the power supplies provide a little humming noise and that is normal. If the humming in Von Duprin PS873 power supply is loud follow these steps. Remove the load from the outp...:
Does the wire size of an EPT affect the operation of an EL device?
Resolution:
Since most wire transfer devices such as an EPT or electric hinges cannot provide large gauge wires, we take the small gauge wire into account when determining the overall wire size for the device....:
What size wire and run is recommended when using a PS914-2RS?
Resolution:
For Product Shipped Prior to August 2012 using the old (black) potted module:a. 0-100 ft 14 gauge wireb. 0-200 ft 12 gauge wire&nbs...:
What is the power output of a 4600 operator?
Resolution:
The 4600 Series operator has both a 12VDC and 24VDC output rated at 1A (combined load) to power strikes, maglocks, and other devices, but an EL device "always" has to have a separate PS914-2RS Seri...:
Why would the horn sound when the solenoid tries to engage on a Von Duprin Chexit device?
Resolution:
Make sure the proper power supply (PS873 or PS914) and proper gauge and run wire is used for Chexit devices shipped prior to 8-24-2015 with solenoid driven. Related Solution: What wire&n...:
How do I wire an EL device to normally hold open the latch and release it during a fire alarm?
Resolution:
Use a normally closed fire alarm as the input to the power supply option board (PS873-2 or PS914-2RS), this will hold the latch retracted. During a fire alarm, the contact will open, dropping...:
CX will not arm. Red light on solid waits 10 sec, light goes out and cycle repeats
Resolution:
Inadequate power or wrong gauge wire is used. The inrush current demand by CX will overload and shutdown the power supply if undersized. You must use the Von Duprin PS873 or...: