Answer
Does a SEH require a door closer?
Resolution:
The SEH is an "electronic holder" (ONLY) that is used to hold open a Fire Rated opening. It requires a door closer to be mounted on the opposite side. It is normally used on an existing opening wit...:
Does LCN still make a 4010SE / 4110 SE?
Resolution:
The LCN 4010SE / 4110 SE series are obsolete, and on longer available (discontinued around Aug 1995). They were replaced by the 4040SE series.The 4010SE / 4110 SE track is replaced w...:
What special template (ST) is used with a 4040(XP) Rw/PA mount closer and a GJ overhead stop?
Resolution:
The use of a 62A Shoe (required) would be used to mount a 4040XP Parallel Arm with a "SURFACE" GJ 70, 79, 81, 90, or 450 series stop. You would order the 4040XP with a Reg w/62A arm op...:
What special template (ST) is used with the 2030 closer and a low profile track and roller?
Resolution:
The 2030 closer requires a minimum 1-3/8" top rail on the door for the standard track. For a top rail less than 1-3/8" and as narrow as 1", you could use the l...:
Can I use a Glynn Johnson 410 with a 4040 regular (pull side) mount?
Resolution:
ST-1630 is required when mounting a 4041 or 4040XP door closer regular (pull/hinge) side with a concealed GJ100 or GJ410 series over head stop.This ST also REQUIRES the use of a 4040-18TJ drop plat...:
What special template (ST) is used with a 4110 closer and GJ90 series?
Resolution:
ST-2730 is used with a 4110EDA closer and GJ901-904 overhead stop.This can only be used with GJ901-904.If a drop plate is required, a 4010-18 drop plate would be used (A 4110-18 drop plate can not ...:
What special template (ST) is used with a 2030 closer and GJ over head stop?
Resolution:
Special template ST-2211 is used to mount a 2030 series closer with a GJ 70,79,81,90, and 450 series overhead stops. This ST works with any GJ "surface" mounted stop. The 2030 closer cannot b...:
Can a magnet, or sentronic device, be released and close the door from a button at a desk?
Resolution:
If a door is being held open by the LCN SEM 7800/1900 magnet or any ME/SE Series Sentronic LCN closer, you can remotely release that door to close by ordering the following parts and wiri...:
Can I mount an LCN Cush closer with an GJ overhead stop?
Resolution:
It would be unnecessary to use the CNS/Cush arm and the Glynn Johnson overhead devices in the same application, both mechanisms stop the door.:
Can a 4040 regular mount installed on the pull side and a Glynn Johnson 90 be mounted together?
Resolution:
The LCN 4041/4040XP and the Glynn Johnson 90 series can be mounted in conjunction with each other without a special template. The 4040 door closer is on the pull side of the door and the GJ 90 is ...:
Can a 4110 EDA and a Glynn Johnson 100 be used together?
Resolution:
A special template is not needed, the closer drops down far enough on the door where it does not conflict with the GJ100 series concealed overhead stop. :
What is the mounting difference between a 2010 closer and a 2030 closer?
Resolution: