Question
Answer
The Von Duprin PS914 power supply must be used on the EL devices with either the 900-2RS or 900-4RL option board since the EL devices requires power supplies set at 24VDC to be able to provide the ...
  You can use a Von Duprin PS914 power supply with any of the following option boards depending on the application. 900-2RS board  will power 1 or 2 devices that do not require timing from pow...
The 8200 can not supply the power needed on an EL dev ice. The EL device requires a Von Duprin PS914-2RS or PS914-4RL power supply or the older Von Duprin PS873-2 or PS873-4TD models.
  For Product Shipped Prior to August 2012 using the old (black) potted module: a.       0-100 ft 14 gauge wire b.      0-200 ft 12...
 
Following items could cause the DC output on PS914 series power supply to drop when access control is activated. Wrong gauge wire from power supply to the the power transfer. Excessive wire run...
For devices shipped after 8-24-2015 with motor driven:  a.       0-200 ft, use  #18 gauge wire b.      0-500 ft, use #14 gauge wir...
For Product Shipped prior to 8-24-2015 with solenoid driven:          a.       0-100 ft, use #14 Gauge Wire      b.&n...
The 8200 Series operator CANNOT power a strike, maglock, or EL device. A separate power supply is ALWAYS required. There is an onboard relay to control a strike, maglock, or EL device.
The 4600 Series operator has both a 12VDC and 24VDC output rated at 1A (combined load) to power strikes, maglocks, and other devices, but an EL device "always" has to have a separate PS914-2RS Seri...