sr swing fire alarm
”
RELATED FAQS
Question
Answer
FIRE ALARM
Resolution:
FA:
What is a 85445-900?
Resolution:
The 710095-00 (85445-900) and 84570-900 are the older Sr. Swing analog (non-digital) control. It is replaced by the current Sr. Swing digital control box. If you need to replace an old ...:
Why does my Chexit device open without sounding the alarm?
Resolution:
:
What will cause no output of 24V on the 900-2RS?
Resolution:
Checking the following items: The setting of the PS914 is set on 24VDC You measure 24VDC from the PS914 mother board The 900-2RS is plugged into the PS914 power power supply Either the fire a...:
Common wiring diagrams
Resolution:
Electronic Protocols: Access Control Door with electric trim Access Control with electric strike Access control with electric strike and LCN 460...:
What is a Knox-Box?
Resolution:
A Knox-Box or Fire Department 911 Box is a small wall-mounted safe that holds building keys for Fire Departments, Emergency Medical Services, and sometimes police to retrieve in emergency situation...:
Why does the PS900 power supply not provide any DC output when AC power light is on?
Resolution:
The following items may cause the PS900 series power supply to have no DC output voltage. 1. If the DC voltage selection jumper is missing, the power supply will not provide any D...:
What is needed to keep the EL device retracted all day?
Resolution:
To keep the Von Duprin electric latch retraction EL or QELA exit device dogged (retracted) all day, have your access control, Key pad, key switch, fire alarm contact or any other signals ...:
What is required to be ordered with the Chexit?
Resolution:
The following are needed for a basic installation: Fire alarm contact is always required with Von Duprin Chexit device. 1 1/4" Mortise cylinder with straight cam is required&nbs...:
Can we run both mag locks and EL devices from the PS 914?
Resolution:
It requires 900-4RL and 900-FA option boards to release the mag locks when a fire alarm is activated. Specify PS914 x 900-4RL x 900-FA.:
What power supply replaces the PS 873 - 4TD?
Resolution:
Option Board Von Duprin PS914 Schlage PS902, PS904, PS906 900-2RS Yes No 900-2Q ...:
Will the FA card mount directly to the PS914?
Resolution:
The 900-FA fire alarm board doesn't mount directly to the PS914 power supply. The 900-8F option board is required with fire alarm board. Fire alarm board plugs to the 900-8F and 900-8F plugs into...:
What is the difference between Panic Hardware and Fire Exit Hardware?
Resolution:
The most obvious difference (in the device) is the lack of mechanical dogging on a Fire Rated Device. There are some internal parts that may be different and the method it is secured to the d...:
Von Duprin Chexit device keeps going into alarm by itself.
Resolution:
Chexit devices shipped with solenoid prior to 8-24-2015. 1. When Chexit device is set for more than zero second rearm time (factory setting is 10 second rearm time) and device goes...:
What replaces the Von Duprin PS873 power supply?
Resolution:
Option Board Von Duprin PS914 Schlage PS902, PS904, PS906 900-2RS Yes No 900-2Q ...:
What are the amperage and power supply requirements for the Von Duprin Chexit (CX) devices?
Resolution:
Chexit motor driven devices shipped after 8-24-2015:You can use 1 Chexit device with PS902, 3 Chexit devices with PS904, and 4 Chexit devices with PS914 or PS906 power supplies with proper gau...:
Where is the cross reference list for PS800 to PS900 series power supplies?
Resolution:
Von Duprin PS914-4RL power supply replaces the PS873-4TD.:
What do I need to use a fire alarm board with a PS914?
Resolution:
The Basic PS914 power supply will not accept a 900-FA fire alarm board. 900-8F option board is required with PS914 power supply to accept 900-FA fire alarm board (900-8F is an adaptor board for...:
Will a Von Duprin Chexit device automatically rearm itself after a fire alarm clears?
Resolution:
The Von Duprin Chexit device will not automatically rearm itself after a fire alarm clears. After a Fire Alarm has triggered the Von Duprin Chexit device, the device must be manually reset&nb...:
How do you get a 4600 Series operator out of "Fire Alarm" mode?
Resolution:
The "Fire Alarm" indication occurs when there is no connection across terminals 13 & 14. Check to verify that the "Fire Alarm" shunt (R1 jumper) on the I/O board has not been cut. Install jumpe...:
How do I wire an EL device to normally hold open the latch and release it during a fire alarm?
Resolution:
Use a normally closed fire alarm as the input to the power supply option board (PS873-2 or PS914-2RS), this will hold the latch retracted. During a fire alarm, the contact will open, dropping...: