senior swing manual

RELATED FAQS

Question
Answer
Surface Mounting - A 9542 DD (double door) header and a 9540-18 mounting plate can be used on the active leaf. A manual closer with a PA (parallel arm) can the be installed on the inactive leaf.  B...
The manual opening force to required to open a Sr Swing operator is approximately 11-12 lbs.
The Senior Swing has a built in circuit that controls closing speed through the motor. If the door is slamming, there must be a broken gear in the gearbox and the gearbox will need to be replaced.
First, turn off the power to the Senior Swing. If the door closes, check controller for a constant activation signal from an activation device. If door continues to hang up and will not close...
A Senior Swing operator can be hard to open manually if "Power Boost" feature is turned on, and programmed to the Cn (continuous) setting. To make the door easy to open manually, turn the "Power Bo...
The older model Senior Swing came with 2 spring options. The "standard force" spring required 15 lbs of manual  opening force, and reduced force "RF" required 11 lbs of manual opening force.  All S...
LCN does offer a 2810 Senior Swing / 2010 manual closer combo for a pair of doors.  Both units contained within the same Senior Swing header. To order a paired operator with a 2810 on&nb...
The 710095-00 (85445-900) and 84570-900 are the older Sr. Swing analog (non-digital) control. It is replaced by the current Sr. Swing digital control box.The following is required when replacing an...
The current (digital control box) activation input wiring harness (# 761464-00) is included in the Sr. Swing parts bag (-518), and has 4 wires in it, Black, White, Yellow, & Gray. This harness p...
The 9550 series Senior Swing WILL NOT work on a pair of doors with auto flush bolts. The 9560 series Senior Swing and a sequence module are required when used on an pair of door with auto flush b...