Question
Answer
What would cause a 4600 Series operator to open up and intermittently stick open?
Resolution:
If manually it opens and closes fine, check to make sure one of the actuators is not getting stuck in the on position. Verify that the "Operating Indicator" LED's -- "POWER and SAFETY CLEAR" LED's ...:
Why would the controller on my 4600 (4630/4640) have no lights on display when powered with 120 VAC?
Resolution:
Verify that the 120VAC is present at the controller (measure 120VAC on the 2 wire gray cable from I/O board to controller -- red/black wires in gray cable). If present, but no lights on the contr...:
Why is my Von Duprin CX going into a weak alarm after the rearm delay?
Resolution:
Chexit devices shipped prior to 8-24-2015 with solenoid - the solenoid pulls and drops, the alarm sounds, there is a solid LED or no LED light after the rearm t...:
Does the ID3D HandKey and HandPunch have a red/green verification light like the F-Series?
Resolution:
Yes, the ID3D does have a red/green LED light option. It's used to indicate successful (green) or rejected (red) hand reads. The part number is GL-100 and it can only be installed in th...:
What is an error code E04 on an LCN 4600?
Resolution:
An error - E 04 - is an indication of a constant activation input from either the "Hold Open" switch or a "Wall Activation" switch when the 4600 power is turned on. This condition also occurs when ...:
How do you adjust the hold open time on a 4600 (4630/4640) operator?
Resolution:
To adjust the hold open time on a 4600 (4630/4640) operator: Press the "MODE" button on the control box 1 time to get into programming mode. The "YELLOW" mode indicator LED next to "HOLD OPEN TI...:
Why does the Schlage button light up “Green” when I open the door?
Resolution:
When unlocking the CO200 door by mechanical key override, the green led will be continuously ON until the key is released. This will occur after firmware CO.A.6 (or later) has been installed int...: