removable rated transom panel

RELATED FAQS

Question
Answer
An Astragal is an applied molding attached most commonly to the meeting edge of doors to: Protection against weather conditions Minimize the passage of light between the doors Retard the passa...
Decorative metal panels can only be attached if the panel manufacturer is UL listed in UL’s category GVUZ. All installation, sizes and hourly ratings are in accordance with that manufacturers” ...
On fire rated transom and/or sidelight frames and fire rated window frames, Steelcraft labeling procedures only control the O/A width and/or height of the frames based on wall condition. The amount...
Transom panels are available in the following constructions: 1 3/4" thick panels with interior construction similar to an L-Series door installed into a frame either Without a transom bar - r...
NO - Louvers are not approved for installation in a fire rated transom / side panel frames.  NFPA Pamphlet 80 - paragraph # 6.3.4.4 states “Louvers shall not be installed in either transom or s...
Maximum hourly rating for a transom and side light or panel frame is 1 1/2 hour (90 minutes). In masonry wall application the maximum is 13'6" x 12'2" In stud wall application the maximum is 13...
Side Light and Side Panel frames - Side Light and Side Panel frames are not KD (Knock Down), they must be assembled and welded. All side lite and side panel frames must be assembled and welde...
Steel transom panels are available: 1 3/4" thick panels - supplied in L-Series (L20, L18 or L16-Series) laminated construction. Recommended down sizing is as follows: Without Transom Bar 3...
Steelcraft doors and/or frames do not contain any asbestos. Steelcraft did use asbestos in the following products: Steelcraft S16-Series stile and rail door with flush panel and UL fire door l...
Astragals are required on: 3 hour fire rated pairs: Double doors - swinging in the same direction Double Egress - swinging in opposite directions Fire rated Dutch Doors Fire rated 1 3/4" t...