rated frame with transom

RELATED FAQS

Question
Answer
Astragals are required on: 3 hour fire rated pairs: Double doors - swinging in the same direction Double Egress - swinging in opposite directions Fire rated Dutch Doors Fire rated 1 3/4" t...
Elevation frames are available in: F-Series (F16 or F14) FN-Series (FN16 or FN14) MU-Series (MU16, MU14) Additional parameters of the frame components: Perimeter (Head and Jambs) Frame: ...
NO - Louvers are not approved for installation in a fire rated transom / side panel frames.  NFPA Pamphlet 80 - paragraph # 6.3.4.4 states “Louvers shall not be installed in either transom or s...
No. Fire rated double egress frames must be a stand alone 3 sided frame assembly. If transom lights and/or sidelights are required, they must be built and installed as separate Fire Window assemb...
Maximum hourly rating for a transom and side light or panel frame is 1 1/2 hour (90 minutes). In masonry wall application the maximum is 13'6" x 12'2" In stud wall application the maximum is 13...
ASTM E-119 is a test standard for walls, partitions and floor or roof systems: This test standard is also used for ceramic type glasses when used as window wall and/or borrowed light frames. ...
The following size limitations per frame unit, are in enforced for welded elevation frames shipped from the factory. These limitations are in place due to the physical size of shipping tr...
Transom panels are available in the following constructions: 1 3/4" thick panels with interior construction similar to an L-Series door installed into a frame either Without a transom bar - r...
On fire rated transom and/or sidelight frames and fire rated window frames, Steelcraft labeling procedures only control the O/A width and/or height of the frames based on wall condition. The amount...