QEL with PS by others
”
RELATED FAQS
Question
Answer
Is the 871-2Q board required on QEL devices when using the PS 873 AO to operate my QEL devices?
Resolution:
The QEL exit devices that were shipped prior to August, 2012 will only communicate to the PS873 with 871-2Q option board or PS900 series with 900-2Q option board. If you...:
Can I run 4 QEL devices from one PS902?
Resolution:
No, you can only add one 900-2Q option board to the PS902 power supply and 900-2Q only can support two QEL devices.:
What are the wire gauge and length requirements for QEL devices?
Resolution:
Use #18 gauge wire up to 200 feet maximum distance from PS900 x 900-2Q power supply to the QEL exit device. The new QEL+ no longer requires the 900-2Q board but still needs a different option board...:
Will the Von Duprin PS902 power supply operate the QEL device?
Resolution:
The Von Duprin PS902 power supply will operate the QEL device as long as you also use the 900-2Q board for devices shipped prior to September of 2012. After July of 2012, the 900-2RS boa...:
How many times can an EL device be operated when using a PS914-2RS with battery backup?
Resolution:
The Von Duprin PS914-2RS retracts the EL or QEL device approximately 200 times with five second hold time after each pull.:
How many Von Duprin QEL devices can be connected to a power supply?
Resolution:
Product Ordered before 7/10/2012 - Product identified by no label on QEL motor. You must use the 900-2Q option board with the PS900 power supplies to operate the QEL devices. The attached ta...:
Will the PS900-2 RS operate the Von Duprin QEL device?
Resolution:
See below for QEL device requirements: QEL devices shipped prior to 7/23/12 must have the 2Q option board for the communication link between the power supply and the exit device. &nb...: