Not flashing connected

RELATED FAQS

Question
Answer
Information on low battery threshold and nuisance delay is noted below: New firmware now has improved levels. - These are approximate values/levels which change with measurement meters and measure...
AD400/AD200/AD250 After ADFwPkg 2.17.0 - June 2011 4 Battery Holder New batteries = 6.2 VDC Low battery threshold is 4.7 VDC for SM & MT - and 3.7 VDC for MAG and PROX (USB stops working at 4...
    AD400/AD200/AD250 After ADFwPkg 2.17.0 - June 2011 8 Battery Holder New batteries = 12.4 VDC Low battery threshold is 7.2 VDC Critical battery threshold is 6.9 VDC Coin cell = new/...
CO2004 Battery Holder (ONLY) New batteries = 6.2 VDC Low battery threshold is 4.2 VDC Critical battery threshold is 3.9 VDC Coin cell = new/full is 3.0 VDC, low is 2.8 VDC
CO2504 Battery Holder (ONLY) New batteries = 6.2 VDC Low battery threshold is 4.2 VDC Critical battery threshold is 3.9 VDC Coin cell = new/full is 3.0 VDC, low is 2.8 VDC
  CO200 & CO250 Disable coin cell Nuisance delay and blink, With CO.A.7 and SUS 4.10.2 or newer for CO200 and CO250, you can use the SUS/HHD, under Lock Properties, Edit, to de-select, DISABLE, t...
A red and green flashing LED's on a QEL indicates the device has been tampered with while power was applied, the push pad was pulled out at least three time. Wait 15 seconds and latchbolt will retr...
The push bar being pulled out three times while power is applied causes the lights to flash and the device to stop retracting.
Check to make sure there is no bind of the latch.
If your Von Duprin EL (solenoid) device pulls and releases quickly instead of holding the latch retracted, please check all of the items below.In most cases, one or more of these solutions will r...
When the "RED" LED on the 8310-865 RF Receiver is blinking, it is receiving an RF signal (interference) from a non programmed device. When receiving this type of signal, it will not program correct...
Followings could cause the Chexit device to go into alarm after the rearm time: Chexit devices shipped after 8-24-2015 with motor driven: Module DPS LED is ON DPS switch contact is open: Close t...
Chexit devices shipped prior to 8-24-2015 with solenoid driven: Chexit device has a RX switch with a connector that needs to be connected to the Chexit module otherwise the alarm will sound af...